B33

List of Holding Registers

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.

 

B052

OV-LAD Stop level of

R/W

Setting the OV-LAD stop level of

10CBh

0 to 10000

0.1 V

 

non stop operation

 

non stop operation. Range is 0.0

 

 

 

 

setting

 

to 1000.0

 

 

 

B053

Deceleration time of

R/W

Range is 0.01 to 3000

10CCh

1 to 300000

0.01 sec

(high)

non stop operation

 

 

 

 

 

B053

setting

R/W

 

10CDh

 

 

(low)

 

 

 

 

 

 

B054

Frequency width of

R/W

Setting of the first quick

10CEh

0 to 100

0.1 Hz

 

quick deceleration

 

deceleration width. Range is 0.0

 

 

 

 

setting

 

to 10.0

 

 

 

B055

DC bus AVR P-gain

R/W

Proportional gain adjustment for

1173h

2 to 50

0.1

 

 

 

DC bus AVR function. Range is:

 

 

 

 

 

 

0.2 to 5.0

 

 

 

B056

DC bus AVR I-time

R/W

Integration time adjustment for

1174h

0 to 1500

0.1s

 

 

 

DC bus AVR function. Range is:

 

 

 

 

 

 

0.0 to 150.0

 

 

 

B080

[AM]analog signal gain

R/W

Adjust of analog output at

10CFh

0 to 255

 

 

 

terminal [AM],

 

 

 

 

 

 

range is 0 to 255

 

 

 

B082

Start frequency

R/W

Sets the starting frequency for

10D1h

5 to 99

0.1 Hz

 

adjustment

 

the inverter output, range is 0.5

 

 

 

 

 

 

to 9.9 Hz

 

 

 

B083

Carrier frequency

R/W

Sets the PWM carrier (internal

10D2h

20 to 120

0.1 Hz

 

setting

 

switching frequency), range is

 

 

 

 

 

 

2.0 to 12.0 kHz

 

 

 

B084

Initialization mode

R/W

Select the type of initialization to

10D3h

0, 1, 2

 

(parameters or trip

 

occur, three option codes:

 

 

 

 

history)

 

00Trip history clear

 

 

 

 

 

 

01Parameter initialization

 

 

 

 

 

 

02Trip history clear and

 

 

 

 

 

 

parameter initialization

 

 

 

B085

Country for

R/W

Select default parameter values

10D4h

 

initialization

 

for country on initialization,

 

 

 

 

 

 

three option codes:

 

 

 

 

 

 

00Japan

 

 

 

 

 

 

01Europe

 

 

 

 

 

 

02US

 

 

 

Page 260
Image 260
Hitachi X200 Series instruction manual Deceleration time Range is 0.01 to