Hitachi X200 Series instruction manual Write in Coil 05h, 10-11, Data Coil Status

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 239
Image 239

B12

The data set in the response is as follows:

Appendix B

 

Response Buffer

4-5

 

 

6-7

 

8-9

 

Register Number

12+0 (high

 

12+0

12+1

 

12+1 (low

12+2

 

12+2 (low

 

 

order)

 

(low

(high

 

order)

(high

 

order)

 

 

 

 

order)

order)

 

 

order)

 

 

 

Register Data

0003h

 

00h

 

00h

 

0063h

 

Trip data

Trip factor (E03)

Not used

Frequency (9.9Hz)

 

Response Buffer

 

10-11

 

 

 

12-13

 

 

14-15

 

Register Number

 

12+3 (high

 

12+3

 

12+4

 

12+4 (low

12+5

 

12+5 (low

 

 

 

order)

 

(low

 

(high

 

order)

 

(high

 

order)

 

 

 

 

 

order)

 

order)

 

 

 

order)

 

 

 

Register Data

 

00h

 

00h

 

 

001Eh

 

 

011Ch

 

Trip data

 

Not used

 

Output current (3.0A)

 

DC-bus voltage (284V)

When the Read Holding Register command cannot be executed normally, refer to the exception response.

Write in Coil [05h]:

This function writes data in a single coil. Coil status changes are as follows:

Data

 

Coil Status

OFF to ON

 

ON to OFF

 

 

Change data (high order)

FFh

 

00h

Change data (low order)

00h

 

00h

An example follows (note that to command the inverter, set A002=03):

Sending a RUN command to an inverter having slave address “8”

This example writes in coil number “1.”

Query:

No.

Field Name

Example

(Hex)

 

 

1

Slave address *1

08

2

Function code

05

3

Coil start address *2

00

 

(high order)

 

4

Coil start address *2

00

 

(low order)

 

5

Change data

FF

 

(high order)

 

6

Change data

00

 

(low order)

 

7

CRC-16 (high order)

8C

8

CRC-16 (low order)

A3

Response:

No.

Field Name

Example

(Hex)

 

 

1

Slave address

08

2

Function code

05

3

Coil start address *2

00

 

(high order)

 

4

Coil start address *2

00

 

(low order)

 

5

Change data

FF

 

(high order)

 

6

Change data

00

 

(low order)

 

7

CRC-16 (high order)

8C

8

CRC-16 (low order)

A3

Note 1: No response is made for a broadcasting query.

Note 2: The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31 are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1 less than the Coil Number.

When writing in a selected coil fails, see the exception response.

Page 239
Image 239
Hitachi X200 Series instruction manual Write in Coil 05h, 10-11, Data Coil Status