Monitoring Trip Events, History, & Conditions

Fault Detection and Clearing

The microprocessor in the inverter detects a variety

 

STOP

 

of fault conditions and captures the event,

 

 

Run

RESET

Stop

recording it in a history table. The inverter output

RUN

 

 

turns OFF, or “trips” similar to the way a circuit

 

 

STOP

breaker trips due to an over-current condition.

 

 

 

 

RESET

Most faults occur when the motor is running (refer

Fault

Trip

Fault

to the diagram to the right). However, the inverter

could have an internal fault and trip in Stop Mode.

 

 

 

In either case, you can clear the fault by pressing the Stop/Reset key. Additionally, you can clear the inverter’s cumulative trip history by performing the procedure Restoring Factory Default Settings” on page 6–8(setting B084=00 will clear the trip history but leave inverter settings intact).

Error Codes

An error code will appear on the display automatically when a fault causes the inverter to trip. The following table lists the cause associated with the error.

 

Error

Name

Cause(s)

 

 

Code

 

 

 

 

 

 

E 01

Over-current event while at

The inverter output was short-circuited, or the

 

 

 

constant speed

motor shaft is locked or has a heavy load. These

 

 

E 02

Over-current event during

conditions cause excessive current for the inverter,

 

 

 

deceleration

so the inverter output is turned OFF.

 

 

E 03

Over-current event during

The dual-voltage motor is wired incorrectly.

 

 

 

acceleration

 

 

 

E 04

Over-current event during

 

 

 

 

other conditions

 

 

 

E 05

Overload protection

When a motor overload is detected by the electronic

 

 

 

 

thermal function, the inverter trips and turns OFF

 

 

 

 

its output.

 

 

E 07

Over-voltage protection

When the DC bus voltage exceeds a threshold, due

 

 

 

 

to regenerative energy from the motor.

 

 

E 08

EEPROM error

When the built-in EEPROM memory has problems

 

 

 

 

due to noise or excessive temperature, the inverter

 

 

 

 

trips and turns OFF its output to the motor.

 

 

E 09

Under-voltage error

A decrease of internal DC bus voltage below a

 

 

 

 

threshold results in a control circuit fault. This

 

 

 

 

condition can also generate excessive motor heat or

 

 

 

 

cause low torque. The inverter trips and turns OFF

 

 

 

 

its output.

 

 

E 11

CPU error

A malfunction in the built-in CPU has occurred, so

 

 

 

 

the inverter trips and turns OFF its output to the

 

 

 

 

motor.

 

 

E 12

External trip

A signal on an intelligent input terminal configured

 

 

 

 

as EXT has occurred. The inverter trips and turns

 

 

 

 

OFF the output to the motor.

 

 

 

 

 

 