Configuring Drive Parameters

355

Output Function Summary Table – This table shows all twelve functions for the logical outputs (terminals [11] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 4-34.

Output Function Summary Table

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

00

RUN

Run Signal

ON

When the inverter is in Run Mode

 

 

 

 

 

OFF

When the inverter is in Stop Mode

 

 

01

FA1

Frequency Arrival Type

ON

When output to motor is at the set frequency

 

 

 

 

1–Constant Speed

OFF

When output to motor is OFF, or in any

 

 

 

 

 

 

acceleration or deceleration ramp

 

 

02

FA2

Frequency Arrival Type

ON

When output to motor is at or above the set

 

 

 

 

2–Over frequency

 

frequency, even if in accel. or decel rams

 

 

 

 

 

OFF

When output to motor is OFF, or at a level

 

 

 

 

 

 

below the set frequency

 

 

03

OL

Overload Advance

ON

When output current is more than the set

 

 

 

 

Notice Signal

 

threshold for the overload signal

 

 

 

 

 

OFF

When output current is less than the set

 

 

 

 

 

 

threshold for the deviation signal

 

 

04

OD

Output Deviation for

ON

When PID error is more than the set threshold

 

 

 

 

PID Control

 

for the deviation signal

 

 

 

 

 

OFF

When PID error is less than the set threshold

 

 

 

 

 

 

for the deviation signal

 

 

05

AL

Alarm Signal

ON

When an alarm signal has occurred and has not

 

 

 

 

 

 

been cleared

 

 

 

 

 

OFF

When no alarm has occurred since the last

 

 

 

 

 

 

cleaning of alarm(s)

 

 

06

Dc

Analog Input

ON

When the [O] input value < B082 setting (signal

 

 

 

 

Disconnect Detect

 

loss detected), or the [OI] input current < 4mA

 

 

 

 

 

OFF

When no signal loss is detected

 

 

07

FBV

PID Second Stage

ON

Transitions to ON when the inverter is in RUN

 

 

 

 

Output

 

Mode and the PID Process Variable (PV) is less

 

 

 

 

 

 

than the Feedback Low Limit (C053)

 

 

 

 

 

OFF

Transitions to OFF when the PID Process

 

 

 

 

 

 

Variable (PV) exceeds the PID High Limit

 

 

 

 

 

 

(C052), and transitions to OFF when the

 

 

 

 

 

 

inverter goes from Run Mode to Stop Mode

 

 

08

NDc

Network Detection

ON

When the communications watchdog timer

 

 

 

 

Signal

 

(period specified by C077) has time out

 

 

 

 

 

OFF

When the communications watchdog timer is

 

 

 

 

 

 

satisfied by regular communications activity

 

 

09

LOG

Logic Output Function

ON

When the Boolean operation specified by C143

 

 

 

 

 

 

has a logical “1” result

 

 

 

 

 

OFF

When the Boolean operation specified by C143

 

 

 

 

 

 

has a logical “0” result

 

 

10

ODc

Communication option

ON

No communication between communication

 

 

 

 

error

 

option is detected during a time set in P044

 

 

 

 

 

OFF

Communication is normal

 

 

43

LOC

Low load detection

ON

Motor current is less than the set value of C039

 

 

 

 

 

OFF

Motor current is not less than the set value of

 

 

 

 

 

 

C039

 