442

Alarm Signal

The inverter alarm signal is active when a fault has

occurred and it is in the Trip Mode (refer to the Run diagram at right). When the fault is cleared the

alarm signal becomes inactive.

STOP

RESET

Stop

RUN

STOP

RESET

Operations and Monitoring

We must make a distinction between the alarm

Fault

Trip

 

signal AL and the alarm relay contacts [AL0], [AL1]

Fault

and [AL2]. The signal AL is a logic function, which

Alarm signal active

you can assign to the open collector output terminal

 

[11] or the relay outputs.

The most common (and default) use of the relay is for AL, thus the labeling of its terminals. Use an open collector output (terminal [11]) for a low-current logic signal interface or to energize a small relay (50 mA maximum). Use the relay output to interface to higher voltage and current devices (10 mA minimum).

Option

Terminal

Function Name

State

 

Description

 

Code

Symbol

 

 

 

 

 

 

 

05

AL

Alarm Signal

ON

 

when an alarm signal has occurred and has not

 

 

 

 

 

 

been cleared

 

 

 

 

OFF

 

when no alarm has occurred since the last

 

 

 

 

 

clearing of alarm(s)

 

Valid for inputs:

11, AL0 – AL2

 

 

Example for terminal [11] (default output

Required settings

C026, C036

 

 

configuration shown – see page 3-54):

Notes:

 

 

 

 

Inverter output

 

By default, the relay is configured as normally

 

 

 

terminal circuit

AL

closed (C036=01). Refer to the next page for an

 

 

 

explanation.

 

 

 

 

 

In the default relay configuration, an inverter

power loss turns ON the alarm output. the

CM2

11

alarm signal remains ON as long as the external

 

 

control circuit has power.

 

 

When the relay output is set to normally closed,

 

RY

a time delay of less than 2 seconds occurs after

 

 

 

powerup before the contact is closed.

 

 

Terminal [11] is an open collector output, so the

Example for terminal [AL0], [AL1], [AL2] (requires

electric specifications of [AL] are different from

output configuration – see page 4-35 and 3-54):

the contact output terminals [AL0], [AL1],

Inverter logic

AL

[AL2].

This signal output has the delay time (300 ms

circuit board

 

 

 

nominal) from the fault alarm output.

 

 

The relay contact specifications are in “Control

AL0 AL1 AL2

Logic Signal Specifications” on page 4–6. The

contact diagrams for different conditions are on

 

 

the next page.

Power

Load

 

supply

 

 

See I/O specs on page 4-6

Page 181
Image 181
Hitachi X200 Series instruction manual Alarm Signal, Or the relay outputs