ERROR CODES LISTING FOR “WS” MODELS
E1 SHORT CYCLE SITUATION: Defined as a compressor that starts and stops more frequently than it should.
E2 KEYBOARD STUCK ERROR: If any key button is stuck or pressed for 20 seconds or more, the unit considers it stuck. If a key is stuck it will be ignored until released. If the “Mode” key is stuck, the unit’s function will default to Cool mode.
E3 FROST PROBE OPEN: Normal operation is allowed. Ohm frost probe. Replace if Ohm value not read. If Ohm value is present replace the board.
E4 FROST PROBE SHORT: Normal operation is allowed. Replace probe.
E5 INDOOR PROBE OPEN: Control assumes indoor ambient temperature is 90 degrees F and unit will operate. Ohm indoor probe. Replace probe if Ohm value is not present.
E6 INDOOR PROBE SHORT: Control assumes ambient temperature is 90 degrees F and unit will operate. Replace probe.
(See note and other infomation below)
ERROR CODES LISTING FOR “WE/WY” MODELS
E1 SHORT CYCLE SITUATION: Defined as a compressor that starts and stops more frequently than it should.
E2 KEYBOARD STUCK ERROR: If any key button is stuck or pressed for 20 seconds or more, the unit considers it stuck. If a key is stuck it will be ignored until released. If the “Mode” key is stuck, the unit’s function will default to Cool mode.
E3 AMBIENT (INDOOR) AIR PROBE OPEN OR SHORT: Control will assume ambient temperature is 90 degrees F when in Cool mode and 60 degrees F when in Heat mode. Unit will operate (see note below).
E4 EVAPORATOR TEMPERATURE PROBE OPEN OR SHORT: Normal operation is allowed. Replace probe (see note below).
E5 CONDENSER TEMPERATURE PROBE OPEN OR SHORT: Normal operation is allowed.
Replace probe.
E7 MOTOR OPERATION
E9 HEAT PUMP FAILURE
NOTE: All error codes display for probes open or shorted will allow unit to operate. Unit may ice up if faulty components are not replaced.
Indoor Coil Frost Probe Sensor (WS/WE/WY Models): Disables compressor at 30 degrees F+/- 3 degrees F. Compressor resumes operation when indoor coil temperature reaches 55 degrees F.
Outdoor Coil Frost Probe Sensor (on WY models): Disables the compressor at 30 degrees F. Compressor resumes operation when temperature reaches 43 +/- 5 degrees F.
Indoor Air Probe Sensor (WS/WE/WY Models)”: Control range is 60 degrees F to 90 degrees F +/- 3 degrees F.
REBOOT THE CONTROL PANEL
To reboot the control panel on a WallMaster unit: with the unit on, simultaneously hold down the Mode button and the Temperature Arrow button for approximately 10 seconds. If the panel will reboot, you will hear the fan come on and the temperature window will read 60 degrees. If this happens, all you need to do is turn the unit off for about 10 seconds and then turn it back on to finish the reboot cycle. If the panel does not reboot, you will most likely need to have the panel replaced.