Problem

Possible Cause

Action

 

 

Replace fuse, reset breaker. If repeats, check

 

Fuse blown or circuit tripped

fuse or breaker size. Check for shorts in unit

 

 

wiring & components

 

Power cord not plugged in

Plug it in

Unit does not run

System switch in “OFF” position

Set switch correctly

Inoperative system switch or open

Test for continuity

 

 

control board

 

 

 

Loose or disconnected wiring at

Check wiring & connections. Reconnect per

 

switch, control board or other com-

 

wiring diagram

 

ponents

 

 

Problem

Possible Cause

Action

 

Dirty filter

Clean as recommended in Owner’s Manual

 

 

Check for dirty or obstructed coil. Use

 

Restricted airflow

pressure wash or biodegradable cleaning

 

 

agent to clean

Evaporator coil

Inoperative t-stat or thermistors

Test for continuity

freezes up

Short of refrigerant

De-ice coil & check for leak

 

Inoperative fan motor

Test fan motor & replace if inoperative

 

 

De-ice coil. Check temp. differential (delta T)

 

Partially restricted capillary tube

across coil. Touch test coil return bends for

 

 

same temp. Test for low running current

Problem

Possible Cause

Action

 

Excessive heat load

Unit undersized. Test cooling performance &

 

replace with larger unit if needed

 

 

 

Restriction in line

Check for partially iced coil & check

 

temperature split across coil

 

 

Compressor runs

 

Check for oil at silver soldered connections.

Refrigerant leak

Check for partially iced coil. Check split across

continually & does

not cycle off

 

coil. Check for low running amperage

 

T-stat contacts stuck

Check operation of t-stat. Replace if contacts

 

remain closed.

 

 

 

T-stat incorrectly wired

Refer to appropriate wiring diagram

 

 

 

 

Thermistor shorted

Replace thermistor or electronic control board

 

 

 

Problem

Possible Cause

Action

 

 

Disconnect power to unit. Remove cover

 

T-stat contacts stuck

of t-stat & check if contacts are stuck. If so,

 

 

replace t-stat

T-stat does not

T-stat set at coldest point

Turn to higher temp. setting to see if unit

cycles off

 

turn unit off

 

 

Incorrect wiring

Refer to appropriate wiring diagrams

 

 

 

 

 

Unit undersized for area to be

Refer to industry standard sizing chart

 

cooled

 

 

 

Defective thermistor

Replace thermistor or electronic control board

 

 

 

34

Page 36
Image 36
Friedrich 2008, 2009 service manual Replace fuse, reset breaker. If repeats, check

2009, 2008 specifications

Friedrich 2008 and 2009 represent significant advancements in heating and cooling technology, particularly in the realm of air conditioning systems. Friedrich is known for producing robust and efficient HVAC solutions tailored for both residential and commercial applications. These models are particularly noteworthy for their innovative features and energy-efficient technologies that enhance user comfort and lower operational costs.

One of the main characteristics of the Friedrich 2008 and 2009 models is their emphasis on energy efficiency. Both units are designed to meet or exceed Energy Star standards, which indicates that they use less energy compared to standard models, contributing to greener living solutions. The incorporation of efficient compressors and high SEER (Seasonal Energy Efficiency Ratio) ratings ensures that users save money on their electricity bills while enjoying optimal cooling performance.

The units also feature advanced inverter technology, which allows for variable speed operation. This means that the system can adjust its cooling capacity based on the current temperature needs, resulting in more consistent comfort while reducing wear and tear on the equipment. Additionally, the inverter technology operates more quietly compared to traditional systems, making these models suitable for both home environments and commercial settings.

Friedrich 2008 and 2009 also provide users with enhanced control options. The inclusion of smart technology and Wi-Fi connectivity allows for remote monitoring and temperature adjustments via smartphones or tablets. Users can create schedules, set temperature preferences, and receive maintenance alerts, contributing to a more user-friendly experience.

Moreover, these models are designed with robust construction, featuring durable materials that withstand various weather conditions. Their compact footprint and sleek design make them suitable for window installation, while an array of sizes accommodates spaces of different dimensions.

Additionally, the air filtration systems in Friedrich 2008 and 2009 units improve indoor air quality. They effectively capture dust, allergens, and other particulates, ensuring a healthier environment for occupants.

In summary, Friedrich 2008 and 2009 models stand out for their energy efficiency, innovative inverter technology, smart controls, and robust construction. With a focus on user comfort and environmental responsibility, these models provide reliable solutions for effective heating and cooling in diverse applications.