Check code

Check code name

Cause of operation

[P19] / [08]

4-way valve operation error

1.

4-way valve error

(TCC-L / AI-NET)

 

2.

TS1 sensor/TE1 sensor error

 

 

3.

Pd sensor/Ps sensor error

 

 

4.

TE sensor/TL sensor misconnection

Check code

Check code name

Cause of operation

[P20] / [22]

High-pressure protective operation 1.

Pd sensor error

(TCC-L / AI-NET)

2.

Service valve closed.

 

3.

Indoor/outdoor fan error

 

4.

Indoor/outdoor PMV clogging

 

5.

Indoor/outdoor heat exchanger clogging

 

6.

SV2 circuit error

Sub-code:Detected outdoor unit No.

Is 4-way valve coil

NO

connector connected?

 

 

YES

 

 

 

 

 

 

Correct connector connection.

(4-way valve coil: CN317)

Correct connector connection.

7.

SV4 circuit error

8.

SV5 circuit error

9.

Outdoor I/F P.C. board error

10.

Operation error of check valve of main

 

discharge pipe

11.

Refrigerant overcharge

159

Are TS1, TE1, Pd, Ps sensor

NO

connectors connected?

 

 

YES

 

 

 

 

 

NO

Are characteristics of resistance value

 

of TS1 and TE1 sensors normal?

 

 

YES

 

 

 

 

 

NO

Are output voltage characteristics

 

of Pd and Ps sensors normal?

 

 

YES

 

 

 

 

 

NO

Are connection and installation

 

of TE1 and TL sensors correct?

 

TS1 sensor: CN504

TE1 sensor: CN505 Pd sensor: CN501 Ps sensor: CN500

Replace sensor.

Replace sensor.

Correct connection

and installation.

Are service valves fully opened?

YES

Are characteristics of

high-pressure sensor normal?

YES

Check mispiping of discharge gas/

suction gas main pipes.

Normal

Check operation of PMV3 SV12.

Normal

Is the flow selector unit normal?

Normal

Reset power supply, and start a test operation corresponded to the season.

NO

NO

Abnormal

Abnormal

Abnormal

All cooling operation ÆTo

B

All heating operation To

C

Open service valves fully.

Check parts.

Failure ÆReplace

Correct piping.

Replace defective parts.

Repair the flow selector unit.

YES

B All cooling operation

*1.

Pressure by pressure gauge (Check joint)

2.

Pressure display on 7-segment display

3.

Output voltage of I/F P.C. board

 

If 1 and 2, 3 are different, an error of pressure sensor is considered.

Reset the power supply and start heating test operation.

Does cooling outdoor fan normally operate?

YES

Is there no fan crack or coming-off?

If 2 and 3 are different, check I/F P.C. board.

NO

Correct faulty parts.

YES

Correct faulty parts.

Is the flow selector unit normal?

YES

Does 4-way valve operate?

NO

4-way valve error

NO

YES

Does refrigerant gas

NO

 

 

discharge to suction side

 

 

 

 

 

 

through 4-way valve? *1

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Check 4-way valve.

Replace the FS unit.

If an error did not occur in test operation, restart the operation.

NO

Is outdoor PMV1, 2 normal?

YES

Are there any obstructions to the operation of the heat exchanger?

1.Blocked heat exchanger

2.Air short circuit

NO

Is SV2 circuit normal?

YES

Is SV4 circuit normal?

(Connector connection, fan IPDU, fan motor, wiring)

NO

Correct faulty position.

(Connector connection wiring, coil mounting, valve clogging, etc)

YES

Eliminate the interfered causes.

NO

Repair SV2 circuit.

(Coil error, clogging, disconnection of cable, etc.)

NO

Repair SV4 circuit.

*1 Check TS and TE temperature of the outdoor unit which compressors is operated.

(I/F) SW01=[1], SW02=[6], SW03=[2]

TS sensor temperature

SW01=[1], SW02=[7], SW03=[2]

ÆTE sensor temperature

Judgment criteria

TE sensor: Normal if TE 20˚C except summer season (Outside temp 20˚C or lower)

TS sensor: Normal if TS 40˚C except summer season (Outside temp 20˚C or lower)

YES

Does the check valve of the main discharge pipe operate normally?

YES

Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition

(Coil error, clogging, disconnection of cable, etc.)

NO

Repair check valve. ÆReplace