Toshiba MMU-AP0091H service manual 144

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 144
Image 144

Check code

Check code name

Cause of operation

[F04] / [19]

TD1 sensor error

TD1 sensor Open/Short

(TCC-L / AI-NET)

This check code means detection of Open/Short of TD1 sensor.

Check disconnection of connector (TD1 sensor: CN502, White) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)

If sensor is normal, replace outdoor I/F P.C. board.

Check code

Check code name

Cause of operation

[F05] / [A1]

TD2 sensor error

TD2 sensor Open/Short

(TCC-L / AI-NET)

This check code means detection of Open/Short of TD2 sensor.

Check disconnection of connector (TD2 sensor: CN503, Pink) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)

If sensor is normal, replace outdoor I/F P.C. board.

Check code

Check code name

Cause of operation

 

[F06] / [18]

TE1 sensor error

TE1 sensor Open/Short

144

(TCC-L / AI-NET)

 

 

 

 

 

 

 

 

This check code means detection of Open/Short of TE1 sensor.

 

 

 

 

Check disconnection of connector (TE1 sensor: CN505, Green) and characteristics of sensor resistance value.

 

(Refer to Outdoor unit temperature sensor characteristics.)

 

 

If sensor is normal, replace outdoor I/F P.C. board.

 

 

 

 

 

 

 

 

 

 

Check code

Check code name

Cause of operation

 

 

 

 

 

[F07] / [18]

TL sensor error

TL sensor Open/Short

 

(TCC-L / AI-NET)

 

 

 

 

 

 

This check code means detection of Open/Short of TL sensor.

Check disconnection of connector (TL sensor: CN521, White) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)

If sensor is normal, replace outdoor I/F P.C. board.

Check code

Check code name

Cause of operation

[F08] / [1b]

TO sensor error

TO sensor Open/Short

(TCC-L / AI-NET)

This check code means detection of Open/Short of TO sensor.

Check disconnection of connector (TO sensor: CN507, Yellow) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)

If sensor is normal, replace outdoor I/F P.C. board.

Check code

Check code name

Cause of operation

[F10] / [0C]

Indoor TA sensor error

TA sensor Open/Short

(TCC-L / AI-NET)

This check code means detection of Open/Short of TA sensor.

Check disconnection of connector (TA sensor: CN104, Yellow) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)

If sensor is normal, replace indoor P.C. board.

Check code

Check code name

Cause of operation

[F12] / [A2]

TS sensor error

TS1, TS2 sensor Open/Short

(TCC-L / AI-NET)

 

 

 

 

 

Sub-code:01: TS1 sensor

02 : TS2 sensor

 

This check code means detection of Open/Short of TS sensor.

Check disconnection of connector (TS1 sensor: CN504, White TS2 sensor: CN522, Black) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature sensor characteristics.)

If sensor is normal, replace outdoor I/F P.C. board.

Check code

 

Check code name

Cause of operation

 

 

 

 

[F13] / [43]

 

TH sensor error

IGBT built-in sensor error in A3-IPDU

(TCC-L / AI-NET)

 

 

 

 

 

 

 

Sub-code:01: Compressor 1 side

02: Compressor 2 side

 

This check code means IGBT built-in temperature sensor error.

Check connection of connectors CN06 on IPDU P.C. board and CN600 on I/F P.C. board.

If sensor is normal, replace IPDU P.C. board.

Page 144
Image 144
Toshiba MMU-AP0091H service manual 144