8-5-2.Operation from remote controller is not accepted and a check code is dis- played on 7-segment display of the interface P.C. board of the outdoor unit.

Remote

7-segment

 

 

 

 

 

 

 

 

 

display of

Cause

 

 

 

 

 

 

Countermeasures

controller status

 

 

 

 

 

 

outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No response

L08

Line addresses and indoor addresses of all the connected

Set up addresses.

 

 

 

indoor units are unset.

 

 

 

 

 

 

 

 

 

 

There is no outdoor unit of group control.

 

 

 

 

 

 

Set up group address.

 

 

 

 

 

 

 

 

 

 

 

E19-00

Indoor unit power is not turned on.

 

 

 

 

 

 

Turn on the power again.

 

 

 

 

 

 

 

 

 

(In order of indoor

outdoor)

 

 

Indoor/outdoor communication line is not correctly connected

Correct wiring.

 

 

 

to the outdoor unit. (Fig. 1)

 

 

 

 

 

 

 

 

 

 

(Indoor/outdoor cannot communicate before address setup.)

 

 

 

 

There is none of outdoor terminator resistor,

 

 

 

 

 

 

Check SW30 bit 2 of the outdoor unit.

 

 

or there are two or more resistances.

ON

 

No connection between multiple refrigerant lines:

 

 

1 2

 

 

 

 

(Before address setup)

 

 

 

 

 

 

SW30 bit 2 0N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection between multiple refrigerant lines:

 

 

 

 

 

 

 

 

 

SW30 bit 2 of the connected outdoor unit is

 

 

 

 

 

 

 

 

 

 

 

 

SW30

turned on only in one line.

 

 

 

 

 

 

E20-01

Address setup is performed with connecting indoor/outdoor

Correct wiring.

 

 

 

communication line between outdoor units. (Fig. 3)

 

 

 

 

 

 

 

 

 

 

Address setup is performed under condition of connecting

Correct wiring.

 

 

 

between multiple refrigerant lines. (Fig. 3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-5-3.There is no display of a check code on 7-segment display on the interface P.C. board of the outdoor unit though there is indoor unit which does not accept the operation from the remote controller.

Remote

7-segment

 

 

display of

Cause

Countermeasures

controller status

outdoor unit

 

 

 

 

 

 

 

 

 

No response

None

Communication line is not connected between indoor and

Modify wiring.

 

 

outdoor.

 

 

 

Line and indoor addresses are unset.

Set up address.

 

 

(Unit which does not response to remote controller)

 

 

 

The power of the header unit of the group is not turned on in

Turn on the power.

 

 

indoor group control.

 

 

 

(Unit which does not response to remote controller)

 

 

 

Group address is set up to follower unit in the individual

Set [0] to group address in case of individual

 

 

control. (Unit which does not response to remote controller)

control.

No display on

None

The power is not turned on.

Turn on the power.

remote controller

 

(Unit which is not displayed on remote controller)

 

(No line is output.)

 

 

 

 

Remote controller is not connected with cable.

Correct wiring.

 

 

 

 

(Unit which is not displayed on remote controller)

 

 

 

 

 

 

 

Miscabling of remote controller

Correct wiring.

 

 

(Unit which is not displayed on remote controller)

 

 

 

Remote controller communication circuit error

Remove FASTON terminal connected to remote

 

 

(Unit which is not displayed on remote controller)

controller terminals (A/B), and check the voltage.

 

 

If 230V is incorrectly applied to the remote controller terminal,

If voltage is not applied, replace P.C. board.

 

 

the remote controller communication circuit fails.

(15 to 18V usually)

 

 

 

 

8-5-4.In check for No. of connected outdoor units and connected Indoor units after address setup, diminished No. of connected units displayed. (There are outdoor/indoor units which do not operate in a test operation.)

Status

Cause

Countermeasures

Number of

Miswiring of communication line between

After modification of wiring, set up address again and check No. of the

connected outdoor

outdoor units or unconnected cable (Fig. 4)

connected outdoor units.

units is short.

(Address setup operation has finished

 

 

without recognition of miswired follower unit.)

 

 

 

 

Number of

Miswiring of communication line between

After modification of wiring, set up address again and check No. of the

connected indoor

indoor units or unconnected cable (Fig. 5)

connected indoor units.

units is short.

(Address setup operation has finished

 

 

without recognition of miswired indoor unit.)

 

Number of outdoor

Remote controller is not connected with wire.

Using the main remote controller connected to a group, start a test operation,

units connected to

Miscabling of remote controller

specify the unit which does not operate (Unit unconnected to group), and then

group is short in

 

check wiring.

group operation

 

 

Remote controller communication circuit

Using the main remote controller connected to a group, start a test operation,

from remote

error

specify the unit which does not operate (Unit unconnected to group).

controller.

If 230V is incorrectly applied to the remote

Remove Fasten receptacle connected to remote controller terminals (A/B),

 

 

controller terminal, the remote controller

and check the voltage. If voltage is not applied, replace P.C. board.

 

communication circuit fails.

(15 to18V in normal time)

 

 

 