No.

Item

 

Operation explanation and applied data, etc.

Remarks

 

 

 

 

8

Release valve

(1) SV2 gas balance control

 

 

control

In order to decrease the starting load on the compressor, SV2 valve

 

 

 

is opened during the time the compressor is ‘OFF’, and the gas is

 

 

 

balanced.

 

 

 

 

(2) SV2 high pressure release control

 

 

 

This function limits the pressure level during the low frequency

 

 

 

operation of the inverter.

 

 

 

(3) SV2 low pressure release control

 

 

 

This function is used to prevent rapid pressure drop during transient

 

 

 

operation of the unit. This is performed by the header unit only. The

 

 

 

function is performed when required, except during ‘No demand’

 

 

 

status or when the system is in ‘Standby’.

 

 

 

(4) SV41, SV42 valves

 

 

 

1) SV41, 42 low-pressure release control

 

 

 

This function is used to prevent pressure dropping to low.

 

 

 

The function is performed during defrost operation, heat start up,

 

 

 

all cooling operation, or mainly cooling or part heating operation.

 

 

 

Control contents (Defrost/heating start pattern)

 

 

 

 

Turn on SV41 and SV42 when PS pressure 0.1MPa, and turn

 

 

 

 

off SV41 and SV42 when PS pressure 0.15MPa.

 

 

 

Control contents (All cooling operation, Mainly cooling, part

 

 

 

 

heating operation)

 

 

 

 

Turn on SV41 and SV42 when PS pressure 0.14MPa and Pd

 

 

 

 

pressure

1.8MPa, and turn off SV41 and SV42 when PS

 

 

 

 

pressure

0.24MPa and Pd pressure 2.2MPa

 

 

 

2) High pressure release control

 

 

 

This function is for gas bypass control which emergently prevents

 

 

 

the high pressure cut.

 

 

 

Turn on SV41 and SV42 when Pd pressure 3.5MPa, and turn off

 

 

 

SV41 and SV42 when Pd pressure 3.45MPa.

 

 

 

(5) SV6 valve

 

 

 

 

1) Cooling bypass control

 

 

 

This function is a liquid refrigerant bypass control to suppress the

 

 

 

rise of the discharge temperature or the inside temperature of the

 

 

 

compressor.

 

 

 

 

Turn on SV6 valve when the discharge temperature (TD1 or TD2)

 

 

 

becomes 96°C or higher and turns off when it drops below 84°C

 

 

 

by bypassing liquid refrigerant.

 

 

 

(6) PMV3

 

 

 

 

1) High pressure release control (All heating operation)

 

 

 

This function suppresses the rise of high pressure during the

 

 

 

inverter low frequency operation when in all heating operation

 

 

 

mode.

 

 

 

 

Set up PMV3 opening to 45 pulses when Pd pressure = 3.45MPa.

 

 

 

2) High pressure release control (All cooling operation)

 

 

 

Set up PMV3 opening to 60 pulses when Pd pressure = 3.5MPa.

 

 

 

 

 

9

Frequency

(1) High pressure release control

 

 

release

This function is to correct the operation command of the compressor

 

 

control

and suppress the rise of high pressure.

 

 

 

1) Control contents

 

 

 

The operation frequency is decreased by 1 step when Pd pres-

 

 

 

sure 3.4MPa. It is decreased by 1 step every 10 seconds until

 

 

 

Pd pressure drops below 3.4MPa.

 

 

 

2) Release condition

 

 

 

• When Pd pressure 3.2MPa

 

 

 

When refrigerant recovery control starts in all heating mode

 

 

 

• During defrost operation, stop, thermo OFF

 

 

 

 

 

 

 

67