8. How to set up the terminal resistance

When all the address setups have finished in the same refriger-

ant circuit system, put the terminal resistance in the same

central control line into one.

Header unit interface P.C. board

ON 1 2

SW30

Manual address setup from remote controller

In case to decide an address of the indoor unit prior to finish of indoor wiring work and unpracticed outdoor wiring work (Manual setup from remote controller)

• Remain only SW30-2 of the header outdoor unit with address

1 as ON. (With end terminal resistance)

SW30

Arrange one indoor unit and one remote controller set to 1 by 1.

1 Push simultaneously SET + CL + TEST buttons for 4 seconds or more.

Set up SW30-2 of the other header outdoor units to OFF. (Without terminal resistance)

9.Connect the relay connector between [U1, U2] and [U3, U4] of the header unit for each refrigerant line.

10.Then set up the central control address.

(For the central control address setup, refer to the Installation manual of the central control devices.)

 

 

ON

3

 

4

 

ON

3

4

 

ON

3

 

4

 

ON

3

 

4

 

 

 

 

 

1

2

 

 

 

1

2

 

 

1

2

 

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW11

 

 

 

 

SW12

 

 

 

SW13

 

 

 

 

SW14

 

 

 

 

ON

3

 

4

 

ON

3

 

4

 

ON

 

ON

3

 

4

 

ON

3

 

4

 

1

2

 

 

1

2

 

 

1

 

 

1

2

 

 

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW06

 

 

 

 

SW07

 

 

SW08

 

 

 

SW09

 

 

 

 

SW10

 

 

Turn on the power.

(Wiring example in 2 lines)

#1

#2

Outdoor

 

Outdoor

LCD changes to flashing.

(Line address)

2 Using the setup temp. / buttons, set ￿ to the item code.

3 Using the timer time / buttons, set up the line address.

90

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

Header

 

 

Follower unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Follower unit

 

 

 

 

 

Header unit

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header unit

 

 

 

 

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

U5

U6

 

 

U1

U2

 

U5

U6

 

 

 

 

U1

U2

 

 

U5

U6

 

 

U1

U2

 

U5

U6

 

 

 

U1

U2

 

 

U5

U6

 

 

 

Before address setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

During setup of address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

 

 

 

U1

U2

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

 

 

 

U1

U2

 

 

 

 

 

 

 

 

 

U1

U2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

A

B

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

 

 

Remote

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

controller

 

 

controller

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

Individual

 

 

 

 

 

 

 

 

 

 

Group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header

 

 

Follower unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Follower unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header unit

 

 

 

 

Header unit

 

 

 

 

 

U3 U4

 

 

 

 

U3 U4

 

 

 

 

 

 

 

U3 U4

 

 

 

 

U3 U4

 

 

 

U3 U4

 

 

1

2

1

2

1

2

1

2

1

2

 

 

Indoor

Indoor

Indoor

 

Indoor

Indoor

 

 

 

 

 

 

 

 

Line address

1

1

1

2

2

Indoor address

1

2

3

1

2

Group address

1

2

2

2

2

 

 

Remote

 

Follower

 

 

 

controller

 

 

Header

In the above example, under condition of no inter-unit wire of the remote controller, set the address after individual connect- ing of the wired remote controller.

(Match it with the line address on the interface P.C. board of the outdoor unit in the identical refrigerant line.)

4 Push SET button.

(OK when display goes on.)

(Indoor address)

5 Using the setup temp. / buttons, set ￿! to the item code.

6 Using the timer time / buttons, set up the indoor address.

7 Push SET button.

 

SW30

ON

 

SW30

ON

 

SW30

ON

 

SW30

ON

 

SW30

ON

 

OFF

 

OFF

 

OFF

 

OFF

 

OFF

 

 

 

 

 

 

 

 

 

 

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

After address setup

Relay

 

 

 

 

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

connector

 

 

 

 

 

 

 

 

 

connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

 

U1

U2

 

 

 

 

 

U1

U2

 

 

 

U1

U2

 

 

 

 

U1

U2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

A

B

 

 

 

 

 

 

A

B

 

 

 

 

A

B

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote

Remote

 

 

 

Remote

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

 

 

controller

controller

 

 

 

controller

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

Individual

 

 

 

 

Group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor interface

 

Header unit

Follower unit

 

Header unit

 

 

Follower unit

 

Header unit

Setup at shipment

P.C. board

 

 

 

 

 

 

from factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW13, 14

 

1

 

 

 

 

 

(Setup is

2

 

 

 

 

 

(Setup is

3

 

 

 

 

1

(Refrigerant line address)

 

 

 

unnecessary.)

 

 

 

unnecessary.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW30-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal-end resistance

 

 

 

 

 

ON

 

 

(Setup is

 

OFF after

 

 

 

 

(Setup is

 

OFF after

ON

of indoor/outdoor communi

 

 

 

 

unnecessary.)

address setup unnecessary.)

address setup

cation line/central control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communication line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect short

 

 

 

 

 

 

Connect short

 

 

 

 

 

 

 

Connect short

 

Relay connector

 

 

 

 

after

 

 

 

Open

 

 

 

after

 

 

 

 

 

Open

 

 

after

Open

 

 

address setup

 

 

 

 

 

 

address setup

 

 

 

 

 

 

 

address setup

 

Group address

Individual : 0000

Header unit : 0001

Follower unit : 0002 } In case of group control

Operation procedure

1 2

3

4 Æ5 Æ6 Æ

7 Æ8

Æ9

Æ10 Æ11 End

 

(OK when display goes on.)

 

 

(Group address)

 

 

8

Using the setup temp.

/

buttons,

 

set ￿" to the item code.

 

 

9

Using the timer time /

buttons, set

 

Individual = ￿￿￿￿ , Header unit = ￿￿￿￿ ,

 

Follower unit = ￿￿￿ .

 

 

10

Push SET button.

 

 

 

(OK when display goes on.)

 

 

11

Push TEST button.

 

 

 

Setup operation finished.

 

 

 

(Status returns to normal stop status.)

Indoor side (Automatic setup)

 

 

 

 

Refrigerant line address

1

1

2

2

3

Indoor unit address

1

2

1

2

1

Group address

0

0

1

2

0

Note

Never connect a relay connector until address setup for all the refrigerant lines has been completed ; otherwise address cannot be correctly set up.

 

 

 

 

CODE No.

 

 

SET DATA SETTING

 

 

 

 

 

UNIT No.

 

2, 5, 8

 

 

R.C. No.

 

Data

 

 

 

 

TEMP.

 

ON / OFF

4, 7, 10

TIMER SET

FAN

MODE

11

 

TIME

SWING/FIX

VENT

 

FILTER

 

 

 

 

RESET TEST SET CL

UNIT

 

Item code

3, 6, 9

1

Page 90
Image 90
Toshiba MMU-AP0091H Turn on the power Wiring example in 2 lines, Push SET button, Group address, Operation procedure