8-6. Test Operation Check

8-6-1. Fan Operation Check

START

Push [START/STOP] button.

Select the operation mode [FAN].

Is air discharged from the

NO

 

discharge port of the indoor unit?

 

 

YES

 

 

 

Is there any abnormal noise?

NO

 

 

 

YES

 

 

 

When an error code has been displayed on the remote controller, refer to Section 8-5-1.

Check indoor fan, fan motor and fan circuit.

(Ensure power has been isolated before removing any covers.)

Check for items in contact with fan.

(Ensure power has been isolated before removing any covers.)

Normal

Check all indoor units in turn.

8-6-2. Cooling/Heating Test Operation Check

The cooling/heating test operation check can be performed on both remote controller and outdoor interface P.C. board.

1. Test operation start/stop operation

Test operation from remote controller

Wired remote controller

1 When pushing TEST button for 4 seconds or more,

 

 

 

 

2,

[TEST] is displayed in the display section and the

 

 

 

 

mode enters the test operation mode.

1,

TEMP.

 

ON / OFF

4

 

 

 

 

 

 

 

TIMER SET

FAN

MODE

 

 

 

TEST

5

TIME

SWING/FIX

VENT

 

 

 

 

 

 

 

 

 

 

 

 

FILTER

 

 

3

2 Push

 

 

RESET TEST SET CL

UNIT

 

ON / OFF

button.

 

 

 

 

 

 

 

 

 

3 Using

MODE button, select an operation mode either [COOL] or [HEAT].

 

 

 

Do not use any other operation modes, only [COOL] or [HEAT].

 

 

 

 

Temperature adjustment is unavailable during test operation.

 

 

TEST

 

 

 

 

 

Errors are detected as usual.

 

 

 

 

 

4

5

When the test operation has finished, push

ON / OFF

button to stop the operation.

 

The same display as that in procedure 1 appears.

Push TEST button to clear the test operation mode.

[TEST] display disappears and the status returns to the normal stop status.