6-2. Outdoor Unit

6-2-1. Operation Start/Operation End

The compressor, solenoid valve, pulse motor valve (PMV), outdoor fan, etc. are controlled by a command from the indoor controller. The follower outdoor unit starts/stops by a command from the header outdoor unit.

No.

Item

Operation explanation and applied data, etc.

Remarks

 

 

 

 

 

1

Pulse Motor Valve

(1) PMV control (using two PMV, 1 and 2)

 

• During heating operation,

 

(PMV) control

• Each PMV is controlled between 90 to 1000 pulses

PMV2 is 0 pulses and

 

 

during operation.

 

 

PMV may be controlled

 

 

• In cooling operation, PMV opening is dependent upon

with only PMV 1, with a

 

 

minimum of 45 pulses.

 

 

detected readings from the TL sensor and Pd pres-

 

 

 

 

 

sure sensor (sub-cool control).

 

 

 

 

• In heating operation, PMV opening is dependent upon

 

 

 

detected readings from the TS and TD sensors and

 

 

 

the Ps pressure sensor (super-heat control).

 

 

 

• Each PMV will be fully closed when the system is in

 

 

 

‘Standby’ or ‘No demand’ modes and when a malfunc-

 

 

 

tion in the system has occurred.

 

 

 

 

 

1000

 

 

 

 

 

PMV opening

 

PMV 2

 

 

 

 

550

 

 

 

 

 

500

 

 

 

 

 

90

PMV 1

 

 

 

 

 

45

 

 

 

 

 

 

 

 

 

 

 

Min.

Med.

Max.

 

(2) PMV3 control

1)

PMV3 (Pulse Motor Valve 3) is controlled between 0

 

 

to 500 pulses during mainly cooling, part heating or

 

 

mainly heating, part cooling operation.

 

2)

PMV3 opening is controlled according to the demand

 

 

capacity difference (HP) between the cooling

 

 

capacity and the total heating capacity.

 

3)

The PMV will be fully closed when the system is in

 

 

‘Standby’ or ‘No demand’ modes and when a mal-

 

 

function in the system has occurred.

 

 

 

2 Outdoor fan control (1) Fan control in all cooling operation

 

1)

The outdoor fan speed/mode is determined by the

When TE temp. (ambient

 

detected Pd pressure value.

temperature) exceeds 25°C,

2)

When cooling operation has started, the outdoor fan

Heating operation stops.

 

speed of the master unit is controlled using the

 

 

detected Pd pressure value.

 

(2) Fan control in all heating operation

 

1)

The outdoor fan speed/mode is determined by the

 

 

detected TE sensor value.

 

2)

If a TE value > 25°C has been continuously detected

 

 

for 5 minutes, the operation may stop.

 

3)

After start up, this control is not available during the

 

 

specified time after a defrost operation.

 

4)

This operation may start and stop repeatedly when

 

 

the system is undercharged.

 

(3) Fan control for mainly cooling, part heating operation

• The maximum fan speed

The outdoor fan speed (mode) is controlled according to

differs depending on the

the target of the Pd (Discharge pressure).

outdoor HP.

64