Check code

 

 

 

 

 

 

 

 

 

 

 

Detected

Check code

Status

Error detection condition

Check item (position)

 

Main

 

Outdoor 7-segment display

AI-NET

 

 

position

name

 

remote

 

 

central control

 

 

 

 

 

 

 

 

 

 

 

 

controller

Check code

Sub-code

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E31

E31

01: IPDU1 error

CF

I/F

IPDU

All stop

Communication of each IPDU

• Check connection of communication connector and

 

 

 

02: IPDU2 error

 

 

communication

 

(P.C. board) in inverter box

disconnection between IPDU and I/F P.C. board.

 

 

 

03: IPDU1, 2 errors

 

 

error

 

interrupted.

• Check outdoor P.C. board (I/F, IPDU, Fan IPDU) error.

 

 

 

04: Fan IPDU error

 

 

 

 

 

• Check external noise.

 

 

 

05: IPDU1 + Fan IPDU error

 

 

 

 

 

• Check power supply P.C. board for fan error.

 

 

 

06: IPDU2 + Fan IPDU error

 

 

 

 

 

 

07:All IPDU error or communication error between IPDU and I/F P.C. board or outdoor I/F P.C. board error

 

F01

OF

Indoor unit

Indoor TCJ

Corresponding

• Resistance value of sensor is

• Check connection/cabling of TCJ sensor connector.

 

 

 

 

 

 

sensor error

unit only stops

infinite or zero. (Open/Short)

• Check characteristics of TCJ sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

 

 

 

 

F02

Od

Indoor unit

Indoor TC2

Corresponding

• Resistance value of sensor is

• Check connection/cabling of TC2 sensor connector.

 

 

 

 

 

 

sensor error

unit only stops.

infinite or zero (Open/Short).

• Check characteristics of TC2 sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

 

 

 

 

F03

93

Indoor unit

Indoor TC1

Corresponding

• Resistance value of sensor is

• Check connection/cabling of TC1 sensor connector.

 

 

 

 

 

 

sensor error

unit only stops.

infinite or zero (Open/Short).

• Check characteristics of TC1 sensor resistance value.

126

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

 

 

F04

F04

19

I/F

TD1 sensor

All stop

• Resistance value of sensor is

• Check connection of TD1 sensor connector.

 

 

 

 

 

 

 

error

 

infinite or zero (Open/Short)

• Check characteristics of TD1 sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

F05

F05

A1

I/F

TD2 sensor

All stop

• Resistance value of sensor is

• Check connection of TD2 sensor connector.

 

 

 

 

 

 

error

 

infinite or zero (Open/Short)

• Check characteristics of TD2 sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

F06

F06

18

I/F

TE1 sensor

All stop

• Resistance value of sensor is

• Check connection of TE1 sensor connector.

 

 

 

 

 

 

error

 

infinite or zero (Open/Short).

• Check characteristics of TE1 sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

F07

F07

18

I/F

TL sensor error

All stop

• Resistance value of sensor is

• Check connection of TL sensor connector.

 

 

 

 

 

 

 

 

infinite or zero (Open/Short).

• Check characteristics of TL sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

F08

F08

1b

I/F

TO sensor

All stop

• Resistance value of sensor is

• Check connection of TO sensor connector.

 

 

 

 

 

 

error

 

infinite or zero (Open/Short).

• Check characteristics of TO sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

F10

OC

Indoor

Indoor TA

Corresponding

• Resistance value of sensor is

• Check connection/cabling of TA sensor connector.

 

 

 

 

 

 

sensor error

unit only stops.

infinite or zero (Open/Short).

• Check characteristics of TA sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

 

 

 

 

F12

F12

01: TS1

A2

I/F

TS1, TS2

All stop

• Resistance value of sensor is

• Check connection of TS1 or TS2 sensor connector.

 

 

 

02: TS2

 

 

sensor error

 

infinite or zero (Open/Short).

• Check characteristics of TS1, TS2 sensor resistance value.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

Page 126
Image 126
Toshiba MMU-AP0091H service manual 126, Status Error detection condition Check item position, Outdoor 7-segment display