Toshiba MMU-AP0091H Case of not setting 01 to Item code 0E, Svs Off, Svd Off, SVD OFF Svdd SVS

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 76
Image 76

nIn case of not setting 01 to Item code “0E”

When more than one indoor unit has been set up as a group to one FS unit and you have forgotten to set 01 on Item code “0E” on all the indoor units, the following may occur:

1)When AUTO operation is selected on the remote controller and cooling operation and heating operation are required, hot air may be discharged from the cooling operation unit or cool air may be discharged from the heating operation unit (or fan stops).

However in case of 2 , “L18” error code is output and the air conditioner stops.

1

 

 

 

 

FS unit

High-pressure gas

High-pressure gas

High-pressure gas

 

Suction

 

 

 

High-

gas pipe

 

 

 

 

 

 

pressure

High-

SVS

High-

High-

gas

pressure

SVSS

pressure

pressure

 

Discharge gas

SVDD

gas

gas

 

gas pipe

Liquid

Liquid

Liquid

 

 

 

 

 

Liquid pipe

SVD

 

 

 

 

 

 

 

Liquid

 

 

 

Indoor unit

 

 

Control wiring between

Heating operation

Cooling operation

Cooling operation

SVD

ON

 

 

 

 

 

 

 

 

 

 

 

indoor unit and FS unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SVDD

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot air

 

Hot air

 

Hot air

SVS

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SVSS

OFF

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

Suction

FS unit

 

 

Low-pressure gas

Low-pressure gas

Low-pressure gas

 

 

 

 

 

 

gas pipe

 

 

 

 

 

 

 

Low-

SVS

 

 

 

 

 

pressure

 

SVSS

 

 

 

Discharge

gas

SVDD

 

Liquid

Liquid

Liquid

 

 

gas pipe

 

 

 

 

 

 

 

 

 

Liquid pipe

 

SVD

 

 

 

 

 

 

 

 

 

 

Liquid

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

Control wiring between

Cooling operation

Heating operation

Heating operation

SVD

OFF

 

 

 

 

 

indoor unit and FS unit

 

 

 

SVDD

OFF

 

 

Cool

Cool

Cool

SVS

ON

 

 

 

 

air

air

air

SVSS

ON

 

 

 

 

 

 

 

2)When the cooling thermostat of the indoor unit that is connected to the FS unit has been off, the refriger- ant will not flow and cooling air may not discharge evenly if the thermostats of the other cooling operation units are on.

3

 

FS unit

Suction

 

gas pipe

 

 

SVS

 

SVSS

Discharge

SVDD

gas pipe

 

Liquid pipe

SVD

 

SVD

OFF

SVDD

OFF

SVS

OFF

SVSS

ON

Indoor unit

Control wiring between indoor unit and FS unit

Cooling operation

Thermo OFF

Cooling operation

Thermo ON

Cooling operation

Thermo ON

76

Page 76
Image 76
Toshiba MMU-AP0091H service manual Case of not setting 01 to Item code 0E, Svs Off, Svd Off, SVD OFF Svdd SVS