7-2-2-1. Power Peak-cut Control (Standard)

Header outdoor unit interface P.C. board

 

 

 

 

SW07

 

 

 

 

Set up Bit 1.

 

 

 

CN513 (BLU)

(Setup

 

 

 

to header

 

 

 

 

unit only)

 

 

Connection cable

 

 

 

 

 

 

 

 

Power peak-cut

 

PJ17 (4P WHI)

 

 

control board

 

 

 

 

 

 

DC

 

 

1.2V

 

OFF

ON

Operation

 

SW2

SW1

Display

In case of serial signal

L1

 

Power

 

In case of pulse signal

supply

Procured

Max. AC240V

locally

Operation

The upper limit capacity of the outdoor unit is restricted based on the demand request signal from outside.

L1 : Display lamp during power peak-cut control

SW1 : Power peak-cut ON switch

(ON during demand, OFF in normal time) 1

SW2 : Power peak-cut OFF switch

(OFF during demand, ON in normal time) 1

*1

Input signals of SW1 and SW2 are acceptable even if they are longer then pulse input (100mm.sec.) or serially made.

However do not turn on SW1 and SW2 simultaneously.

Be sure to prepare a contact for each terminal.

Relay contact capacity of “operation” port

Below AC240V 0.5A (COSØ = 100%) Below DC24V 1A (Non-inductive load)

Note) When connecting non-inductive load such as relay coil to L1 load, insert the noise surge absorber CR (In case of AC) or counter electromotive-proof diode (In case of DC) into the bypass circuit.

Power peak-cut control board: TCB-PCDM2E

Outdoor unit destination to be connected becomes the header outdoor unit (U1).

 

Setup when Power peak-cut control requested

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power peak-cut control board

SW1

SW2

L1

Outdoor unit interface P.C. board

 

 

(TCB-PCDM2E)

SW07: Bit 1 OFF

SW07: Bit 1 ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power peak-cut ON signal is input.

ON

OFF

ON

0% (Forced stop)

Capacity 60% (Upper limit restriction)

 

 

 

 

 

 

 

 

 

 

 

 

Power peak-cut OFF signal is input.

OFF

ON

OFF

100% (Normal operation)

100% (Normal operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup positions of header outdoor unit

 

Connector position detail

interface P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

CN513

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blue

 

 

 

 

 

 

 

 

 

 

 

Switch position detail

SW07

Bit 1

OFF

Operation stop to 100%

 

 

ON

ON 60% to 100%

 

 

82

Page 82
Image 82
Toshiba MMU-AP0091H service manual Power Peak-cut Control Standard, Relay contact capacity of operation port