8-7. Service Support Function

8-7-1. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit

The following functions enables the start and stop of the indoor units using the switches on the interface P.C. board of the header unit.

No.

Function

Outline

Setup/Release

7-segment display

 

 

 

 

 

 

1

All cooling

Changes the mode of all the connected indoor

[Setup]

Section A

Section B

 

test operation

units collectively to cooling test operation.

Push SW04 for 2 seconds or more

[C

]

[

–C]

 

 

Note) Control operation same as test

with SW01”2”, SW02”5”, SW03”1”.

 

 

 

 

 

 

 

 

 

 

 

 

 

operation for remote controller.

[Release]

 

 

 

 

 

 

 

Return SW01, SW02, SW03 to “1”.

 

 

 

 

 

 

 

 

 

 

2

All heating

Changes the mode of all the connected indoor

[Setup]

Section A

Section B

 

test operation

units collectively to heating test operation.

Push SW04 for 2 seconds or more

[H

]

[

–H]

 

 

Note) Control operation same as test

with SW01”2”, SW02”6”, SW03”1”.

 

 

 

 

 

 

 

 

 

 

 

 

 

operation for remote controller.

[Release]

 

 

 

 

 

 

 

Return SW01, SW02, SW03 to “1”.

 

 

 

 

 

 

 

 

 

 

3

Batch start

Starts all the connected indoor units collec-

[Setup]

Section A

Section B

 

 

tively.

Push SW04 for 2 seconds or more

[CH]

[

11]

 

 

Note) The contents follow the setup of remote

with SW01”2”, SW02”7”, SW03”1”.

[ 11] is displayed on

 

 

 

 

 

 

 

controller.

[Release]

Section B for 5 seconds.

 

 

 

Return SW01, SW02, SW03 to “1”.

 

 

 

 

 

 

 

 

 

 

 

Batch stop

Stops all the connected indoor units collec-

[Setup]

Section A

Section B

 

 

tively.

Push SW05 for 2 seconds or more

[CH]

[

00]

 

 

 

with SW01”2”, SW02”7”, SW03”1”.

[ 00] is displayed on

 

 

 

 

 

 

 

 

 

[Release]

Section B for 5 seconds.

 

 

 

Return SW01, SW02, SW03 to “1”.

 

 

 

 

 

 

 

 

 

 

4

Individual

Starts the specified indoor unit.

[Setup]

Section A

Section B

 

start

Notes)

Push SW04 for 2 seconds or more set

[

]

[

]

 

 

SW01 “16” and set SW02 and SW03

Section A:

 

 

 

 

• Control operation same as test.

 

 

 

 

to address No. (1 to 64) to be started.

 

 

 

 

Displays the corresponding

 

 

• The other indoor units keep existing status.

 

 

 

 

 

[Release]

indoor address.

 

 

 

 

 

 

 

 

 

 

Return SW01, SW02, SW03 to “1”.

Section B:

 

 

 

 

 

 

 

 

 

 

 

 

Displays [ 11] for 5 seconds

 

 

 

 

from operation-ON.

 

 

 

 

 

 

 

 

Individual

Stops the specified indoor unit.

[Setup]

Section A

Section B

 

stop

Note) The other indoor units keep existing

Push SW05 for 2 seconds or more set

[

]

[

]

 

 

SW01 “16” and set SW02 and SW03

 

 

 

 

 

 

status.

Section A:

 

 

 

 

to address No. (1 to 64) to be stopped.

 

 

 

 

 

Displays the corresponding

 

 

 

[Release]

indoor address.

 

 

 

 

 

Return SW01, SW02, SW03 to “1”.

Section B:

 

 

 

 

 

 

 

 

 

 

 

 

Displays [ 00] for 5 seconds

 

 

 

 

from operation-OFF.

 

 

 

 

 

 

 

 

Individual test

Operates the specified indoor unit.

[Setup]

Section A

Section B

 

operation

Note) The other indoor units keep existing

Push SW04 for 10 seconds or more

[

]

[

]

 

 

set SW01 “16” and set SW02 and

 

 

 

 

 

 

status.

Section A:

 

 

 

 

SW03 to address No. (1 to 64) to be

 

 

 

 

 

Displays the corresponding

 

 

 

operated.

 

 

 

indoor address.

 

 

 

 

 

[Release]

 

 

 

 

 

Section B:

 

 

 

 

 

Return SW01, SW02, SW03 to “1”.

 

 

 

 

 

Displays [ FF] for 5 seconds

 

 

 

 

 

 

 

 

from test operation-ON.

 

 

 

 

 

 

 

 

NOTE 1) This start/stop function only sends the command signals from the outdoor unit to the indoor unit, such as start, stop, operation mode, etc.

Once it does not resend the signals even if the indoor unit does not follow the sent signals.

NOTE 2) The above controls are not available when an error has caused the system to stop.

Interface P.C. board

7-segment display [A] 7-segment display [B]

SW04

SW05

SW01 SW02 SW03 Rotary switch

102

Page 102
Image 102
Toshiba MMU-AP0091H Service Support Function, Function to Start/Stop ON/OFF Indoor Unit from Outdoor Unit, 102