Toshiba MMU-AP0091H 129, Status, Check all the outdoor units in the corresponding line

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 129
Image 129

129

 

 

Check code

 

 

 

 

 

 

 

 

 

 

 

 

 

Detected

Check code name

Status

Error detection condition

 

Check item (position)

Main

Outdoor 7-segment display

 

AI-NET

 

remote

 

 

 

central control

position

 

 

 

 

 

controller

Check code

Sub-code

 

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H07

H07

 

d7

I/F

Protection for oil

All stop

The operating compressor

Check all the outdoor units in the corresponding line.

 

 

 

 

 

 

level drop detection

 

detected oil shortage

• Check full opening of service valve of balance pipe.

 

 

 

 

 

 

 

 

continuously for 2 hours.

• Check connection and installation of TK1, TK2, TK3, and TK4 sensors.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check characteristics of TK1, TK2, TK3, and TK4 resistance values.

 

 

 

 

 

 

 

 

 

• Check gas leak and oil leak in the same line.

 

 

 

 

 

 

 

 

 

• Check refrigerant stagnation in compressor.

 

 

 

 

 

 

 

 

 

• Check error of SV3A, SV3B, SV3C, SV3D, and SV3E valves.

 

 

 

 

 

 

 

 

 

Check clogging of oil separator oil return circuit.

 

 

 

 

 

 

 

 

 

Check clogging of oil-equation circuit.

 

 

 

 

 

 

 

 

 

<Check clogging of oil equation pipe between compressors.>

 

 

 

 

 

 

 

 

 

• Check TS1, TS2 sensors (Miswiring and misinstallation of TS1 and TS2)

 

 

 

 

 

 

 

 

 

• Check leakage of SV6 circuit.

 

 

 

 

 

 

 

 

 

• Check FS unit.

 

 

 

 

 

 

 

 

 

 

Leakage of check valve of bypass between liquid pipe and discharge gas pipe

 

 

 

 

 

 

 

 

 

 

Mispiping of discharge/suction gas connection

 

 

 

 

 

 

 

 

 

 

Miswiring of SVD/SVS valve/Misinstallation of coil

 

 

 

 

 

 

 

 

 

• Check whether there is no setup missing of indoor unit in all cooling operation mode

 

 

 

 

 

 

 

 

 

 

 

H08

H08

01: TK1 sensor error

 

d4

I/F

Oil level detective

All stop

• Resistance value of

• Check connection of TK1 sensor connector.

02: TK2 sensor error

 

 

 

 

 

 

temp sensor error

 

sensor is infinite or zero.

• Check characteristics of TK1 sensor resistance value.

 

 

03: TK3 sensor error

 

 

 

 

 

 

 

 

 

 

 

(Open/Short)

• Check outdoor P.C. board (I/F) error.

 

 

04: TK4 sensor error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All stop

• Resistance value of

• Check connection of TK2 sensor connector.

 

 

 

 

 

 

 

 

sensor is infinite or zero.

• Check characteristics of TK2 sensor resistance value.

 

 

 

 

 

 

 

 

(Open/Short)

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All stop

• Resistance value of

• Check connection of TK3 sensor connector.

 

 

 

 

 

 

 

 

sensor is infinite or zero.

• Check characteristics of TK3 sensor resistance value.

 

 

 

 

 

 

 

 

(Open/Short)

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All stop

• Resistance value of

• Check connection of TK4 sensor connector.

 

 

 

 

 

 

 

 

sensor is infinite or zero.

• Check characteristics of TK4 sensor resistance value.

 

 

 

 

 

 

 

 

(Open/Short)

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H14

H14

44

I/F

Compressor 2

All stop

Compressor 2 case

• Check compressor 2 case thermo circuit. (Connector, cable, P.C. board)

 

 

 

 

 

 

case thermo

 

thermostat operated.

• Check full opening of service valve. (Gas and liquid side)

 

 

 

 

 

 

operation

 

 

• Check outdoor PMV clogging. (PMV1, 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check SV42 valve leak.

 

 

 

 

 

 

 

 

 

• Check miscabling/misinstallation of SV41 and SV42.

 

 

 

 

 

 

 

 

 

• Check valve opening of indoor PMV.

 

 

 

 

 

 

 

 

 

• Check 4-way valve error.

 

 

 

 

 

 

 

 

 

• Check refrigerant shortage.

 

 

 

 

 

 

 

 

 

• Check SV11 circuit. (Wiring, OFF at one side only)

 

 

 

 

 

 

 

 

 

• Check mispiping of discharge gas/suction gas main pipe.

 

 

 

 

 

 

 

 

 

• Check Flow selector unit.

 

 

 

 

 

 

 

 

 

 

Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.)

 

 

 

 

 

 

 

 

 

 

Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between

 

 

 

 

 

 

 

 

 

 

FS unit and indoor unit, and connection of connectors.

 

 

 

 

 

 

 

 

 

 

Check miswiring of SVS/SVD valves.

 

 

 

 

 

 

 

 

 

 

 

Page 129
Image 129
Toshiba MMU-AP0091H 129, Status, Check all the outdoor units in the corresponding line, Error detection condition