7-1-4. Applied Control in Indoor Unit

nRemote location ON/OFF control box (TCB-IFCB-4E)

[Wiring and setup]

Use the exclusive connector for connection with the indoor control P.C. board.

In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in the group. However when taking out the operation/error signal from the other unit, it is necessary to take out from each unit individually.

(1) Control items

1)

Start/Stop input signal : Operation start/stop in unit

2)

Operation signal

: Output during normal operation

3)

Error signal

: Output during alarm

(Serial communication error or indoor/outdoor protective device) operation

(2) Wiring diagram using remote control interface (TCB-IFCB-4E)

Input

IFCB-4E : No voltage ON/OFF serial signal

Output

No voltage contact for operation, error display

 

Contact capacity: Below Max. AC240V 0.5A

Indoor control P.C. board

Start/Stop input

1

COM (GND)

2

Remote controller prohibition/clear input

3

Operation signal output

4

COM (+12V)

5

Error signal output

6

Remote location ON/OFF control box

(TCB-IFCB-4E)

1

ON/OFF serial

2

signal input

3

 

4

COM

CN06

CN61

T10

(YEL)

1

2

3

4

5

6

Operation signal output

CN13

Error signal output

Power supply 220–240V, ~50Hz