3. Connection check between Flow Selector Unit (FS Unit) and indoor unit

Check list 2

1

 

 

Remote

 

Indoor unit

 

controller

 

 

 

 

 

A

A

U1/U2

B

B

 

Earth terminal

Control

FS unit

 

 

wiring

 

 

CN81

CN02

 

 

 

L

N

Power

CN01

 

 

 

line

 

3

 

 

Earth

Earth terminal

terminal

 

Power supply Single phase 220-240V, 50Hz

Earth leakage

Pull

2

breaker

Box

Power switch

 

 

Indoor unit

Remote

controller

 

 

 

A

A

U1/U2

B

B

Earth terminal

Control

FS unit

 

wiring

 

CN81

CN02

 

 

L N

Power

CN01

 

 

line

 

 

 

Earth

Earth terminal

terminal

 

Pull

 

4

Box

 

Indoor unit

Remote

controller

 

 

 

A

A

U1/U2

B

B

Earth terminal

Control

FS unit

 

wiring

 

CN81

CN02

 

 

L N

Power

CN01

 

 

 

 

line

 

 

 

Earth

Earth terminal

terminal

 

Calculate the additional amount of refrigerant from the following:

 

 

 

Additional amount

 

Actual liquid

Additional amount of

× 1.3

 

Corrective amount of

of refrigerant (B)

=

pipe length ×

refrigerant per liquid pipe 1m

+

refrigerant by system capacity

 

 

                   

 

 

             

 

 

 

(A)

 

 

(B)

Firstly enter the total length for each liquid pipe in the following table and then calculate the additional amount of refrigerant by pipe length.

Additional amount of refrigerant by pipe length

Pipe dia at

Standard amount of refrigerant

Total pipe length at each liquid side

Additional amount of refrigerant pipe

liquid side

kg/m

dia at each liquid side

kg

 

 

 

 

 

 

Ø 6.4

0.025 ×

=

 

kg

 

 

 

 

 

Ø 9.5

0.055 ×

=

 

kg

 

 

 

 

 

Ø 12.7

0.105 ×

=

 

kg

87

No.

Main check items

Check

Are indoor/outdoor communication lines connected to U1/U2 terminals?

Is the signal line of the FS unit connected to connector CN81?

ƒIs the power supply cable of the FS unit connected to R (L) and S (N) terminals?

Is the power supply cable of the FS unit connected to the closed end connector?

When the indoor unit is a Wall type (1 Series) or Concealed Duct High Static Pressure type?

Note) The above figure does not cover all the electric wirings.

For details, refer to the Installation Manual of Flow selector unit.

Check list 1

• Using the “Check list 1”, check there is no trouble in the installation work.

Is capacity of the leak

Outdoor total capacity

XXXX

A

Header unit (A)

XXXX

A

Indoor unit

XXXX

A

breaker appropriate?

 

 

 

Follower unit (B)

 

 

A

 

 

 

 

 

 

 

 

XXXX

 

 

 

 

 

 

 

 

 

Follower unit (C)

XXXX

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the diameter of the power cable correctly wired?

Header unit (A)

 

 

mm²

Indoor unit

 

 

mm²

XXXX

XXXX

 

 

 

 

Follower unit (B)

XXXX

mm²

 

 

 

 

 

 

 

 

 

Follower unit (C)

XXXX

mm²

 

 

 

 

 

 

 

 

 

 

 

 

Is the control communication line correctly wired?

Indoor –outdoor connection terminals (U1, U2)

 

 

 

 

XXXX

 

 

 

 

Outdoor–outdoor connection terminals (U5, U6)

 

XXXX

 

 

 

 

 

Central control system connection terminals (U3, U4)

XXXX

 

 

 

 

 

 

 

 

 

 

 

Is the power of the indoor units supplied collectively?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the earth grounded

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the insulation good? (10Mor more)

 

 

 

Mor more

 

 

 

 

 

XXXX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the main power voltage correct? (Within 200V ± 10%)

 

 

V

 

 

 

 

 

 

XXXX

 

 

 

 

 

Is the diameter of the connecting pipe correct?

Is the branch kit correct?

Does the indoor unit condensate drain adequately?

Is the thermal insulation of pipes good? (Connecting pipes, Branch kit)

For both indoor and outdoor units, ensure air is not short-circuited from discharge to inlet ports.

After pressure test, check that the pipework and indoor units have been vacuumed and the correct amount of additional gas has been charged.

Are valves of all the outdoor units fully opened?

Suction gas side

Discharge gas side

Liquid side

Balance side

Header unit (A)

 

XXXX

 

 

XXXX

 

 

XXXX

 

 

XXXX

 

Follower unit (B)

 

XXXX

 

 

XXXX

 

 

XXXX

 

 

XXXX

 

Follower unit (C)

 

XXXX

 

 

XXXX

 

 

XXXX

 

 

XXXX

 

• Check the additional amount of refrigerant.

Ø 15.9

0.160 ×

=

kg

 

 

 

 

Ø 19.0

0.250 ×

=

kg

 

 

 

 

Ø 22.2

0.350 ×

=

kg

 

 

 

 

 

 

Additional amount of refrigerant by pipe

kg

 

 

length (A)

 

 

 

 

 

 

 

Next, refer to the following table for the corrective amount of refrigerant (B) by system capacity.

Corrective amount of refrigerant by system capacity

 

 

 

Normal type

 

System horse power HP

 

 

 

 

Unit 1

Unit 2

Unit 3

Corrective amount of refrigerant (B) kg

 

 

 

 

 

 

8

8

 

 

2.0

 

 

 

 

 

10

10

 

 

2.5

 

 

 

 

 

12

12

 

 

3.0

 

 

 

 

 

16

8

8

 

–1.5

 

 

 

 

 

18

10

8

 

0

 

 

 

 

 

20

10

10

 

2.0

 

 

 

 

 

24

8

8

8

–4.5

 

 

 

 

 

26

10

8

8

–3.0

 

 

 

 

 

28

10

10

8

–1.5

 

 

 

 

 

30

10

10

10

0

 

 

 

 

 

Finally add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by system capacity (B). This is the final additional amount of refrigerant.

If the result is indicated as a negative, do not add any refrigerant. Do not add the refrigerant (= 0kg).

Additional amount of refrigerant

Additional amount of refrigerant by pipe length (A)

kg

 

 

Corrective amount of refrigerant by system HP (B)

kg

 

 

Additional amount of refrigerant

kg

 

 

Page 87
Image 87