No.

Item

Operation explanation and applied data, etc.

Remarks

 

 

 

 

10

Compressor

Each compressor is stopped should the Pd pressure sensor reach a

 

 

stop due to

value of 3.5 MPa. This control is performed by the header unit and

 

 

high pressure

any follower units.

 

 

release

 

 

 

 

 

 

11

Case heater

Heating is provided for both the compressor case and accumulator.

 

 

control

When the compressor in any outdoor unit is stopped, the heater is

 

 

 

switched on to prevent accumulation of refrigerant.

 

 

 

After installation of a system, it should be powered for the specified

 

 

 

period of time prior to operating a test run to prevent damage to the

 

 

 

system.

 

 

 

If the system has not been powered for a prolonged period of time, it

 

 

 

is important to apply power for the specified period of time before

 

 

 

resuming operation.

 

 

 

This function is often performed in conjunction with the compressor

 

 

 

winding heating control. When this occurs, a noise may be heard

 

 

 

which is not an indication of a malfunction.

 

 

 

(1) Contents of control

 

 

 

• The function is performed during when the compressor is off.

 

 

 

• When the TO sensor temp measures 28°C or higher the heater

 

 

 

turns off and turns on when it change:measures 25°C or lower

 

 

 

• The heater remains ‘ON’ for 10 minutes after the compressor

 

 

 

has changed mode from Off to On.

 

 

 

 

 

12

IPDU control

The IPDU controls the inverter compressor by communicating a

 

 

 

command frequency that controls the compressor speed, depending

 

 

 

on any active releases.

 

 

 

The main controls of the IPDU P.C. board are:

 

 

 

(1) Current release control

 

 

 

Feedback from the AC input current sensor (CT) is used to

 

 

 

prevent the inverter input current exceeding its specified limit

 

 

 

(2) Heat sink temperature detection control

 

 

 

• Feedback from the thermistor (TH) on the compressor driving

• A TH sensor is

 

 

module is used to prevent the IGBT from overheating. The

provided in each two

 

 

highest value is taken from IPDU 1 and IPDU 2 TH sensors.

IPDU.

 

 

(3) Over-current protective control

 

 

 

• When an over-current condition is detected by the IPDU, the

 

 

 

compressor is stopped.

 

 

 

(4) Compressor case thermo control

 

 

 

• The compressor stops when the compressor case thermostat is

 

 

 

activated.

 

 

 

• Whenever this condition occurs, a 1 count is added to the

• The case thermostat

 

 

system error count.

is normally closed

 

 

• After a period of 2 minutes and 30 seconds, the compressor is

and connected to

 

 

reactivated and the error count cleared if the operation contin-

interface P.C. board.

 

 

ues without further error for a period of 10 minutes or more.

 

 

 

• If the error count reaches 4, the check code [H04] is displayed

 

 

 

(for compressor 1) and [H14] (for compressor 2).

 

 

 

 

 

13

High pressure

(1) High pressure SW control

 

 

prevention

• The high pressure switch is connected to the IPDU board and is

 

 

control

in the normally closed condition.

 

 

 

• When the high pressure switch is activated, the compressor is

 

 

 

stopped.

 

 

 

• Whenever this condition occurs, a 1 count is added to the

 

 

 

system error count.

 

 

 

• After a period of 2 minutes and 30 seconds, the drive to the

 

 

 

compressor is reactivated and the error count is cleared if the

 

 

 

operation continues with further error for a period of 10 minutes

 

 

 

or more.

 

 

 

• If the error count reaches 4, the check code [P04] is displayed.

 

 

 

 

 