Check code

Check code name

Cause of operation

[L07] / [99]

Group line in individual indoor unit

The group line is connected in the

(TCC-L / AI-NET)

 

individual indoor unit.

Check code

Check code name

Cause of operation

 

 

 

[L10] / [88]

Outdoor capacity unset

The model selection jumper of the outdoor I/F

(TCC-L / AI-NET)

 

P.C. board does not match the model.

 

 

 

YES

Is there group wiring?

NO

Check indoor P.C. board.

Failure ÆReplace

Check setup item code

DN 12, 13, and 14 addresses.

YES

Is there an individual indoor unit.

NO

Item code (D1) 12: Line address

Item code (D2) 13: Indoor address

Item code (D3) 14: Group address

Correct indoor group address.

Service I/F P.C. board for the outdoor unit is common to all outdoor units.

The service I/F P.C. board will need to be set up for the correct model based upon the faulty I/F P.C. board, which it is replacing. Set up the model based upon the I/F P.C. board assembly change procedure.

Check code

Check code name

Cause of operation

 

 

 

[L17] / [46]

Inconsistent models of

There are outdoor units on the communication

(TCC-L / AI-NET)

outdoor units

line other than Super Module Multi Flex type

 

 

such as Super Module Multi or Super Module

Check code

Check code name

Cause of operation

[L08] / [99]*

Indoor group / address unset

Indoor address unset

(TCC-L / AI-NET)

Multi ice regenerative type

Are the connected outdoor

NO

152

Is the power on all the

 

NO

indoor units turned on?

 

 

 

YES

 

 

 

 

 

 

 

 

 

Disconnect connectors between

[U1, U2] and [U3, U4].

Clear addresses.

(Refer to “Address clear”.)

Turn on the power of indoor units.

Turn on the power of outdoor unit again.

units those for flex on 1 system?

 

 

(Check model name.)

 

 

YES

 

 

 

 

 

 

Is the check code [L17]

NO

displayed even if turning power on

 

again of all the connected outdoor

 

units on 1 system alone?

 

 

YES

 

 

 

 

 

 

Replace outdoor units of other models with specified models

Correct communication line between outdoor units.

Re-execute address setup. (Refer to “Address setup”.)

Note) This code is displayed when the power is turned on at the first time after installation. (Because the address is not yet set up)

Check code

Check code name

Cause of operation

[L09] / [46]

Indoor capacity unset

Indoor capacity unset

(TCC-L / AI-NET)

Are all the connected

 

NO

 

Change the incorrectly built-in outdoor

 

outdoor I/F P.C. board's on 1 system

 

 

 

 

 

 

 

I/F P.C. board's with I/F P.C. board's for

 

P.C. board's of outdoor units for

 

 

 

 

 

 

 

 

 

Super Module Multi Flex.

 

Super Module Multi Flex?

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check again whether there is any

Using 7-segment on I/F P.C. board, check the model name on each outdoor unit.

other outdoor unit or not on the

communication line in 1 system.

 

For check, when putting the rotary switch on SW01/02/03=16/16/16, it is an

If any, turn off power of the

 

outdoor I/F P.C. board, for Super Module Multi Flex if “F” is displayed at the left

corresponding outdoor unit and

 

side of 7-segment [A] part.

 

 

 

then check once more.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are capacity setups

YES

of indoor units unset?

 

 

NO

 

 

 

 

 

 

Set up capacity data of indoor unit.

(Setup item code (DN) = 11)

Check indoor P.C. board.

Defect Replace