4-2. Explanation of Functional Parts

Functional part name

 

 

 

Functional outline

 

 

 

 

 

 

Solenoid valve

SV3A

(Connector CN324: Red)

 

 

 

 

Closed

: Allows oil to collect/remain in the oil tank.

 

 

 

Open

: Allows oil to exit the oil tank.

 

 

 

 

 

 

 

SV3B

(Connector CN313: Blue)

 

 

 

 

Open

: Allows oil to return to the outdoor unit via the balance pipe.

 

 

 

 

 

 

 

SV3C

(Connector CN314: Black)

 

 

 

 

Open

: Pressurizes the oil tank..

 

 

 

 

 

 

 

 

SV3D

(Connector CN323: White)

 

 

 

 

Open

: Supplies oil to the compressor from the oil separator.

 

 

 

 

 

 

 

SV3E

(Connector CN323: White)

 

 

 

 

Open

: Turns on during operation and balances oil between compressors.

 

 

 

 

 

SV2

(Hot gas bypass) (Connector CN312: White)

 

 

 

1)

Low pressure release function

 

 

 

 

2)

High pressure release function

 

 

 

 

3)

Gas balance function during stop time

 

 

 

 

 

SV4 1

(Gas balance control for compressor start-up) (Connector CN311: Blue)

 

SV4 2

1)

For gas balance start

 

 

 

 

2)

High pressure release function

 

 

 

 

3)

Low pressure release function

 

 

 

 

 

 

 

 

SV5

(Connector CN310: White)

 

 

 

 

1)

Increase of No. of heating indoor units, Gas balance function in defrost time

 

 

2)

Low-pressure balance function of discharge gas pipe during all cooling operation

 

 

 

 

 

 

SV6

(Connector CN309: White)

 

 

 

1)

Liquid bypass function for discharge temp. release (Cooling bypass circuit)

 

 

 

 

 

 

 

 

SV11

(Connector CN322: White)

 

 

 

 

1)

For shutdown discharge gas (During all cooling operation and defrost operation)

 

 

 

 

 

 

SV12

(Connector CN319: White)

 

 

 

 

1)

Flow-rate control function of refrigerant to sub heat exchanger during simultaneous operation

 

 

2)

Flow-rate control function of refrigerant to sub heat exchanger during defrost operation

 

 

 

 

 

4-way valve

 

(Connector CN317: Blue)

 

 

 

 

1)

Cooling/Heating selection

 

 

 

 

2)

Reverse defrost

 

 

 

 

3)

Main-/Sub-heat exchanger selection

 

 

 

 

 

 

Pulse motor

PMV1, 2

(Connector CN300, 301: White)

 

 

valve

 

1)

Super heat control function during all heating operation and mainly heating, partly cooling operation

 

 

2)

Under-cool adjustment function during all cooling operation

 

 

 

3)

Divided flow control function during mainly cooling, partly heating operation

 

 

 

 

 

 

PMV3

(Connector CN302: Red)

 

 

 

 

1)

For flow-rate control of sub heat exchanger during simultaneous operation

 

 

 

(Control function of heating divided flow)

 

 

 

2)

A function preventive high pressure up during all cooling or all heating operation

 

 

 

 

Oil separator

 

1)

Prevention for early drop of oil level (Decrease of flow-out of discharge oil to cycle)

 

 

2)

Reserve function of surplus oil

 

 

 

 

 

 

Temp. sensor

TD1, TD2

(TD1: Connector CN502: White, TD2: Connector CN503: Pink)

 

 

 

1)

Protection of compressor discharge temp.

 

 

 

2)

Releasing of discharge temp.

 

 

 

 

 

 

 

 

TS1

(Connector CN504: White)

 

 

 

 

1)

Controls super heat of PMV1 and 2 during all heating operation and simultaneous operation

 

 

 

 

 

 

TS2

(Connector CN522: Black)

 

 

 

 

1)

Controls indoor oil recovery during all cooling operation and mainly cooling, partly heating operation

 

 

2)

Detects overheat of cycle.

 

 

 

 

 

 

 

 

TE

(Connector CN505: Green)

 

 

 

 

1)

Controls defrost during all heating operation and simultaneous operation.

 

 

2)

Controls outdoor fan during all heating operation and simultaneous operation.

 

 

 

 

 

 

 

TK1, TK2,

TK1: Connector CN514: Black,

TK2: Connector CN515: Green,

 

TK3, TK4,

TK3: Connector CN516: Red,

TK4: Connector CN523:Yellow

 

 

 

1)

Judges oil level of compressor.

 

 

 

 

 

 

 

 

 

 

 

 

TL

(Connector CN521: White)

 

 

 

 

1)

Detects under-cool during all cooling operation and simultaneous operation.

 

 

 

 

 

 

TO

(Connector CN507:Yellow)

 

 

 

 

1)

Detects external ambient temperature.

 

 

 

 

 

 

 

 

49

Page 49
Image 49