8-7-2. Error Clearing Function

1. Clearing from the main remote controller

[Error clearing in outdoor unit]

Error of the outdoor unit is cleared by the unit of one refrigerant circuit system to which the indoor units oper- ated by the remote controller. (Error of the indoor unit is not cleared.)

For clearing errors, the service monitor function of the remote controller is used.

<Method>

1 Change the mode to service monitor mode by pushing CL + TEST buttons simultaneously for 4 seconds or more.

2 Using / buttons, set “FF” to item code.

The display in Section A in the following figure is counted with interval of 5 seconds as “￿￿￿# ￿￿￿" ￿￿￿! ￿￿￿ ￿￿￿￿ ￿￿￿￿ ”.

When the count arrives “￿￿￿￿ ”, the error is cleared.

However, counting from “￿￿￿# ” is repeated on the display.

3 When TEST button is pushed, the status returns to the normal status.

Operation procedure

1 Æ2 Æ3

The status returns to the normal status.

 

 

 

 

CODE No.

Section A

 

UNIT

No.

 

 

R.C.

No.

 

 

 

 

 

TEMP.

 

 

ON / OFF

3

TIMER SET

 

FAN

MODE

TIME

SWING/FIX

VENT

 

FILTER

 

 

 

 

RESET TEST SET CL

 

UNIT

 

1

2

[Error clearing in indoor unit]

Error in the indoor unit is cleared by ON / OFF button on the remote controller.

(Only error of the indoor unit connected with operating remote controller is cleared.)