7-2-2-5. Night Operation Control

Header outdoor unit interface P.C. board

 

 

 

CN508 (4P RED)

 

 

 

 

 

Connection cable

 

 

 

 

 

External master

 

PJ17

(4P WHI)

ON/OFF

 

 

 

 

 

 

 

control board

 

 

 

 

 

 

 

 

HEAT COOL

COM

SMC

Procured locally

Operation

Reduce emitted noise during night by resting the compressor and fan speed.

Terminal

Input signal

Operation

 

ON

Night (sound reduction)

 

 

COOL

OFF

operation control

 

 

 

(SMC)

ON

 

 

 

 

OFF

Usual operation

 

 

The control contents are accepted during leading and trailing of the input signal.

(The status of leading and trailing should be held for 100mm. sec. or more.)

Capacity criterion during night operation control

Capacity during control indicates values as described in the following table.

 

Night operation sound

Capacity

 

reduction dB (A)

COOL

HEAT

 

 

 

 

1201 type

50

Approx. 55%

Approx. 45%

 

 

 

 

1001 type

50

Approx. 65%

Approx. 55%

 

 

 

 

0801 type

50

Approx. 80%

Approx. 70%

 

 

 

 

SMC : Input signal for night operation.

(Against Max. capacity)

External master ON/OFF control board : TCB-PCMO 2E

 

Outdoor unit destination to be connected becomes the header outdoor unit (U1).

 

7-2-2-6. Operation Mode Selection Control

Header outdoor unit interface P.C. board

 

 

 

CN510 (4P WHI)

 

 

 

 

 

Connection cable

 

 

 

 

 

External master

 

PJ17

(4P WHI)

ON/OFF

 

 

 

 

 

 

 

control board

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

 

 

 

COM

 

 

 

 

 

SMC

SMH

Operation

This control can be operated with the operation mode which is permitted by SMC or SMH.

The indoor unit operating by operation mode without permission is as follows:

1)Display on remote controller

(Mode select controlled)” goes on.

2)Indoor fan

In FAN mode: Fan normally operates.

In COOL mode: Fan normally operates.

In HEAT mode: Fan operates with ultra low speed.

*Be sure to prepare a contact for each contact terminal. Outside signal: No voltage serial contact

SMC: COOL mode designated input switch

SMH: HEAT mode designated input switch

External master ON/OFF control board : TCB-PCMO 2E

Outdoor unit destination to be connected becomes the header outdoor unit (U1).

Procured locally

85

Page 85
Image 85