10-2-1. Outdoor Interface P.C. Board Dip switch function exchange setup list

 

Part type

 

 

 

 

 

Exchange contents

Initial setup

 

 

 

 

 

 

at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW01

Rotary SW 4bit 16 step

Display / Operation switch (1)

 

For 7-segment display / service operation

[1]

 

 

 

 

 

 

 

 

 

 

 

SW02

Rotary SW 4bit 16 step

Display / Operation switch (2)

 

For 7-segment display / service operation

[1]

 

 

 

 

 

 

 

 

 

 

 

SW03

Rotary SW 4bit 16 step

Display / Operation switch (3)

 

For 7-segment display / service operation

[1]

 

 

 

 

 

 

 

 

 

 

 

SW04

Push SW

For service [Operation/Start]

 

[Operation/Start] by pushing

 

 

 

 

 

 

 

 

 

 

 

SW05

Push SW

For service [Stop/End]

 

 

[Stop/End] by pushing

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

Backup setup

 

 

 

(Based on the following setup)

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2

 

Bit 4

 

Bit 3

Bit 2

Bit 1

 

OFF

 

 

 

 

 

 

 

 

 

 

 

SW06

SW 4bit

Bit 3

 

OFF

 

OFF

OFF

OFF

Normal

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

 

 

OFF

ON

No.1 COMP backup

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

OFF

No.2 COMP backup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

Power peak-cut control exchange

 

OFF: 0 – 100%, ON: Middle – 100%

OFF

 

 

 

 

 

 

 

SW07

SW 4bit

Bit 2

Power peak-cut control exchange (Expansion)

(For 4-steps exchange)

OFF

 

 

 

 

 

 

 

 

 

Bit 3

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

n Header unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

Outdoor address setup exchange

 

OFF: Auto setup (Normal), ON: Manual setup

OFF

 

 

 

 

 

 

 

 

 

SW09

SW 4bit

Bit 2

Judge indoor capacity over

 

 

OFF: YES (Normal), ON: NO

OFF

 

 

 

 

 

 

 

 

 

 

 

Bit 3

Correction of installed pipe size

 

OFF: Normal, ON: Size UP

OFF

 

 

 

(For outdoor expansion)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

Judge abnormal No. of connected indoor units

OFF: No error judgment, ON: Error

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

Bit 2

Outdoor fan high-static pressure shift

 

OFF : Normal, ON: High-static pressure shift

OFF

SW10

SW 4bit

 

 

 

 

 

 

 

 

 

Bit 3

 

 

 

 

 

 

OFF: Normal,

OFF

 

 

 

 

 

 

 

 

 

 

Sound reduction control

 

 

ON : INV frequency upper limit restriction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

 

 

 

 

 

 

OFF: Normal, ON: Fan rpm upper limit restriction

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 2

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

SW11

SW 4bit

Bit 3

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

Bit 4

Operation when indoor overflow detected

OFF: System stop,

OFF

 

 

ON : System operation continues

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

PMV manual operation selected

 

OFF: PMV1, PMV2

OFF

 

 

 

ON : PMV3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW12

SW 4bit

Bit 2

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

Bit 3

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 1

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

SW13

SW 4bit

Bit 2

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

Bit 3

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4

Line address setup

 

 

 

 

OFF

 

 

 

 

 

 

 

SW14

SW 4bit

Bit 1, 2, 3, 4

Line address setup

Refer to item “Address setup procedure”

OFF

 

 

 

 

 

 

 

 

 

 

 

SW30

SW 2bit

Bit 2

Terminator resistor between outdoor units

OFF: No Terminator resistor

ON

ON : Exists

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN30

Check connector

Manual full opening setup of PMV

 

 

Opened: Normal, Short: Opened fully

Open

 

 

 

 

 

 

 

CN31

Check connector

Manual full closing setup of PMV

 

 

Opened: Normal, Short: Opened fully

Open

 

 

 

 

 

 

 

CN32

Check connector

Check for assembly line in factory.

 

 

Opened: Normal, Short: Check mode

Open

 

 

 

 

 

 

 

 

 

 

 

*The outdoor unit connected with indoor/outdoor communication line becomes automatically the master unit. No manual setting is necessary.