Toshiba MMU-AP0091H service manual 160, P22 / 1A Outdoor fan Ipdu error

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 160
Image 160

160

C

All heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

Is connector

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does heating indoor fan

 

 

 

 

 

connection of indoor

 

 

 

 

 

 

 

 

 

 

 

 

normally operate?

 

 

 

 

 

 

 

 

heat exchanger fan or

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

fan motor normal?

 

 

 

 

 

 

 

NO

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is indoor PMV normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair faulty parts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

Are characteristics

 

 

NO

 

 

Is connector connection

 

 

 

 

 

 

 

 

 

 

 

of sensor TC2 and TCJ

 

 

 

 

 

 

coil normal?

 

 

 

 

resistance normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair faulty parts.

 

 

 

 

 

 

Replace TC2 or TCJ sensor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there a clogging?

 

 

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Faulty ÆReplace

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace PMV body

 

 

 

 

 

 

 

 

 

 

Repair check valve. ÆReplace

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is check valve of main

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair check valve. ÆReplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

discharge pipe normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are there

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

any obstructions to the

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation of the heat exchanger?

 

 

 

 

 

 

 

 

 

 

 

Eliminate the interfered causes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Air filter clogging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Blocked heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Air short circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is SV5 circuit normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair SV5 circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil error, choke,

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(disconnection of cable, etc. )

 

 

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check operation of 4-way valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace 4-way valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check clogging of SV11 circuit.

 

 

 

 

 

 

 

 

 

 

 

 

Replace defective parts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are there indoor units connected

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check and correct cabling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to different refrigerant circuits?

 

Use the mis-wiring check function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

( of outdoor unit.

 

 

)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant overcharge,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

clogging, pipe breakage,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

abnormal overload condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check code

Check code name

Cause of operation

[P22] / [1A]

Outdoor fan IPDU error

1. Fan lock

(TCC-L / AI-NET)

 

2.

Fan IPDU P.C. board error

 

 

3.

Overload

 

 

4.

External cause such as power surge

 

 

5.

Fan IPDU power P.C. board error

Sub-code:

0

: IGBT short circuit

1

: Position detect circuit error

 

3

: Motor lock error

4

: Motor current error detected

 

C

: TH sensor error (Heat sink overheat)

D

: TH sensor error

 

E

: Vdc error

 

 

Are wire connections on the fan IPDU

NO

Correct cable connector connection.

and the power P.C. board assembly normal?

 

 

 

 

 

YES

 

 

 

 

 

 

 

YES

Is the outdoor fan motor locked?

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

NO

 

 

Is winding resistance of the motor correct?

 

Replace motor.

 

 

13 to 33W(Between R and S, R and T, S and T)

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

YES

 

 

 

 

 

Is the fan IPDU firmly attached to the heat sink.

Retightening of screws, etc.

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

YES

 

 

 

 

Is sub-code of outdoor I/F P.C. board [0d]?

Replace fan IPDU.

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

YES

 

Is there no problem such as stuffing or

 

Correct cause of overload.

 

 

blast blowing to discharge port of outdoor fan?

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check fan IPDU.

 

 

 

 

 

 

 

 

 

 

Page 160
Image 160
Toshiba MMU-AP0091H service manual 160, P22 / 1A Outdoor fan Ipdu error