17. P.C. BOARD

17-1. Indoor Unit

17-1-1. Exchange of P.C. Board for Indoor Service

Part code

Model type

P.C. board model

Label display on P.C. board

 

 

 

 

 

 

 

MMU-AP✻✻1WH series

 

 

 

 

 

MMU-AP✻✻1YH series

 

 

 

 

 

MMU-AP ✻✻1SH series

 

 

 

 

431-6V-207

MMD-AP✻✻1H series

MCC-1403

 

03RD M01

 

 

MML-AP✻✻1H series

 

 

 

 

 

 

 

 

 

 

MMU-AP✻✻1BH series

 

 

 

 

 

MMF-AP✻✻1H series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

431-6V-210

MMD-AP✻✻1BH series

MCC-1402

 

03DD M02

 

 

 

 

 

 

 

 

MMU-AP✻✻1H series

 

 

 

 

 

MMC-AP✻✻1H series

 

 

 

 

431-6V-269

MMK-AP✻✻1H series

MCC-1402

 

03DD M03

 

 

MMD-AP✻✻1SPH/SH series

 

 

 

 

 

 

 

 

 

 

MMU-AP✻✻2SH series

 

 

 

 

 

 

 

 

 

 

Requirement when exchanging the P.C. board assembly for indoor service

The fixed memory (herein EEPROM, IC10) stores the model type and capacity code, which are set upon shipment from the factory.

Data set upon installation (i.e. line/indoor/group addresses) are also stored in the EEPROM. Proceed with the exchange of the P.C. board as shown in the procedure below.

After exchange, confirm the settings for master/sub, etc. are correct and carry out a test operation.

Exchange procedure

Method 1

Before exchange, it is possible to turn on the power of the indoor unit and read out the setup contents from the wired remote controller.

Readout of EEPROM data: Procedure 1

ò

Exchange of P.C. board for service & power ON: Procedure 2

ò

Programming the EEPROM data: Procedure 3

ò

Power supply reset

(All the indoor units connected to the remote controller are reset in case of group operation control)