8-7-12. Monitor Function of Remote Controller Switch

When using a remote controller with the model name RBC-ATM21E, the following monitor functions can be used.

Calling of display screen

[Contents]

The temperature or the operation status of the remote controller, indoor unit, or each sensor of the outdoor unit can be known by calling up the service monitor mode from the remote controller.

[Procedure]

1 Push CL + TEST buttons simultaneously for 4 seconds or more to call up the service monitor mode. The service monitor goes on, and temperature of the item code ￿￿ is firstly displayed.

2 Push the temperature setup / buttons to select the item number (Item code) to be monitored.

For displayed codes, refer to the table below.

3 Push

UNIT

button to change the item to one to be

 

monitored. Then monitor the indoor unit and sensor temperature or operation status in the correspond- ing refrigerant line.

4 Pushing TEST button returns the display to the normal display.

CODE No.

UNIT No.

TEMP.

 

 

ON / OFF

2

4

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

 

 

 

 

3

FILTER

 

 

 

RESET TEST

SET CL

UNIT

 

1

 

 

 

Operation procedure

1 Æ2 Æ3 Æ4

Returns to the normal display

 

Item

Data name

Unit

Display

 

Item

Data name

Unit

Display

 

code

format

 

code

format

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

Room temp (During control)

°C

 

 

10

Compressor 1 discharge temp (Td1)

°C

× 1

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Compressor 2 discharge temp (Td2)

°C

× 1

 

01

Room temp (Remote controller)

°C

 

 

 

 

 

 

 

 

 

2)

 

 

12

High-pressure sensor detention

MPa

× 100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure (Pd)

(NOTE

02

Indoor suction temp (TA)

°C

× 1

 

 

 

 

4, 5)

 

 

 

 

 

 

 

 

13

Low-pressure sensor detention

MPa

× 100

 

 

 

 

03

Indoor coil temp (TCJ)

°C

× 1

pressure (Ps)

Indoor unit data

individual data (NOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Suction temp (TS)

°C

× 1

04

Indoor coil temp (TC2)

°C

× 1

 

 

 

 

15

Outdoor heat exchanger temp (TE)

°C

× 1

 

 

 

 

05

Indoor coil temp (TC1)

°C

× 1

 

 

 

 

16

Temp at liquid side (TL)

°C

× 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

Indoor discharge temp (Tf) (NOTE 1)

°C

× 1

17

Outside ambient temp (TO)

°C

× 1

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Low-pressure saturation temp (TU)

°C

× 1

 

 

 

 

 

 

08

Indoor PMV opening

pulse

× 1/10

unit

 

 

 

 

 

 

19

Compressor 1 current (I1)

A

× 10

 

 

 

 

 

 

 

 

 

 

Outdoor

 

0A

No. of connected indoor units

unit

 

 

 

 

 

 

 

data

 

1A

Compressor 2 current (I2)

A

× 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0b

Total HP of connected indoor units

HP

× 10

1b

PMV1 + 2 opening

pulse

× 1/10

System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1d

Compressor 1, 2 ON/OFF

(NOTE 3)

0C

No. of connected indoor units

unit

 

 

 

 

 

 

 

 

 

 

1E

Outdoor fan mode

0 to 31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0d

Total HP of outdoor units

HP

× 10

 

 

 

 

 

 

 

1F

Outdoor unit HP

HP

× 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(NOTE 1) Only a part of indoor unit types is installed with the discharge temperature sensor. This temperature is not displayed for other types.

(NOTE 2)

When the units are connected to a group, data of the header indoor unit only can be displayed.

(NOTE 3)

01 : Compressor 1 only is ON.

10 : Compressor 2 only is ON.

11 : Both compressor 1 and 2 are ON.

(NOTE 4)

The item codes are described as the example of the header unit.

 

(NOTE 5)

The upper digit of an item code represents the outdoor unit number.

 

 

1 : Header unit (A)

2 : Follower unit (B)

3 : Follower unit (C)

 

115

Page 115
Image 115
Toshiba MMU-AP0091H Monitor Function of Remote Controller Switch, Calling of display screen, Contents, Procedure, 115