1. Data display of system information (Displayed on the header outdoor unit only)

SW01

SW02

SW03

 

 

 

Display contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

3

Refrigerant name

Displays refrigerant name.

 

 

A

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model with refrigerant R410A

 

 

r4

 

10A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model with refrigerant R407C

 

 

r4

 

07C

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

System capacity

A

[ 5] to [48]

: 5 to 48HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

[HP]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

No. of outdoor units

A

[ 1] to [ 4]

: 1 to 4 units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

[ P]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

No. of connected indoor units/

A

[ 0] to [48]

: 0 to 48 units (No. of connected units)

 

 

 

 

 

 

No. of units with cooling thermo ON

 

 

 

 

 

 

 

 

 

 

 

 

 

B

[C0] to [C48] : 0 to 48 units (No. of units with cooling thermo ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

No. of connected indoor units/

A

[ 0] to [48]

: 0 to 48 units (No. of connected units)

 

 

 

 

 

 

No. of units with heating thermo ON

 

 

 

 

 

 

 

 

 

 

 

 

 

B

[H0] to [H48] : 0 to 48 units (No. of units with heating thermo ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

Compressor command

A

Data is displayed with hexadecimal notation

 

 

 

 

 

 

correction amount

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

Release control

A

Normal time

: [ r], During release control: [r1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

Oil-equalization control

A

Normal time

: [oiL-0]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

During oil equation : [oiL-1]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

Oil-equalization request

A

Displays with segment LED lighting pattern

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

Display A

Display B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

F in the left figure goes on:

 

 

 

 

 

 

 

 

F G B

 

 

Header requests oil equalization.

 

 

 

 

 

 

 

E

C

 

 

C in the left figure goes on:

 

 

 

 

 

 

 

 

 

D Dp U2

 

Follower requests oil-equalization.

 

 

 

 

 

 

 

 

U3 U4

(Outdoor unit number)

 

 

 

 

 

 

 

 

 

 

 

 

10

 

Refrigerant/oil recovery operation

A

During sending of cooling refrigerant oil recovery signal : [C1].

 

 

 

 

 

 

 

Normal time

: [C ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

During sending of heating refrigerant oil recovery signal : [H1].

 

 

 

 

 

 

 

Normal time

: [H ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

Automatic address

A

[Ad]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Automatic addressing : [FF], Normal time : [ ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

Demand operation

A

[dU]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Normal time

: [

]. In 50% to 90% : [ 50 to 90]

 

 

 

 

 

 

 

 

When controlling by communication line input : [E50 to E90]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

Optional control (P.C. board input)

Displays optioned control status

 

 

A

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation mode selection : In heating with priority (Normal)

 

h.

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Priority on cooling

 

 

c.

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating only

 

 

 

 

H.

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling only

 

 

 

 

C.

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Priority on No. of operating indoor units

 

n.

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Priority on specific indoor unit

 

 

U.

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Batch start/stop

: Normal

 

 

..

 

...

 

 

 

 

 

Start input

 

 

 

 

.1.

 

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop input

 

 

 

 

.0.

 

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Night low-noise operation : Normal

 

 

..

...

 

 

 

 

 

Operation input

 

 

 

..

1...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Snow fan operation : Normal

 

 

..

...

 

 

 

 

 

Operation input

 

 

 

..

.1..

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

Option control (BUS line input)

 

Same as above

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

Unused

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mark: Indicates none on display

164

Page 164
Image 164