4-3. Indoor Unit

Liquid side Gas side

Strainer

Capillary tube

 

 

 

 

 

 

 

 

 

Air heat exchanger

 

 

at indoor side

 

Pulse Motor

 

 

 

 

Valve (PMV)

 

 

 

 

 

Distributor

Sensor

 

 

 

 

 

 

Sensor

 

(TCJ)

Fan

 

(TC2)

 

 

 

Sensor

 

 

 

 

 

 

 

 

(TC1)

 

 

Sensor

M

Fan motor

 

 

(TA)

 

 

(NOTE) MMU-AP0071YH to AP0121YH type air conditioners have no TC2 sensor.

Functional part name

 

Functional outline

 

 

 

Pulse Motor Valve

PMV

(Connector CN082 (6P): Blue)

 

 

 

1)

Controls super heat in cooling operation

 

 

 

2)

Controls under cool in heating operation

 

 

 

3)

Recovers refrigerant oil in cooling operation

 

 

 

4)

Recovers refrigerant oil in heating operation

 

 

 

 

Temp. sensor

1.

TA

(Connector CN104 (2P): Yellow)

 

 

 

1)

Detects indoor suction temperature

 

 

 

 

 

2.

TC1

(Connector CN100 (3P): Brown)

 

 

 

1)

Controls PMV super heat in cooling operation

 

 

 

 

 

3.

TC2

(Connector CN101 (2P): Black)

 

 

 

1)

Controls PMV under cool in heating operation

 

 

 

 

 

4.

TCJ

(Connector CN102 (2P): Red)

 

 

 

1)

Controls PMV super heat in cooling operation

 

 

 

2)

[MMU-AP0071 to AP0121YH only]

 

 

 

 

Controls PMV under cool in heating operation

 

 

 

 

 