6. CONTROL OUTLINE

6-1. Indoor Unit

6-1-1. Control Specifications

No.

Item

 

 

 

Outline of specifications

 

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

 

1

Power supply

(1) Identification of outdoor unit

 

 

 

 

 

 

 

 

 

is reset.

 

When the power supply is reset, the outdoor units are

 

 

 

 

individually identified and communication is established.

 

 

 

(2) Check code clear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the power supply is reset, the check code is also reset.

 

 

 

 

If an abnormal status is still present upon restart the check

 

 

 

 

code will be displayed again on the remote controller.

 

 

 

 

 

 

 

2

Operation

(1) Based upon the operation command received from the

Concealed Duct High

 

select

 

remote controller or central controller, the operation mode is

Static Pressure type air

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

conditioner cannot operate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in drying mode.

 

 

 

Remote controller

 

 

 

 

Control outline

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

 

 

 

 

Stops air conditioner.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

 

 

 

Fan only operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

 

 

 

 

Cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY

 

 

 

 

 

 

Dry operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

Heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL/HEAT AUTO

 

 

COOL/HEAT AUTO operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating operation is automatically selected with difference

 

 

 

between the set point temperature and room temperature.

 

 

 

 

 

3

Room temp.

(1) Set point temperature adjustment range on remote controller

 

 

control

 

(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allcooling

 

 

 

All heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired type

 

 

18 to 29°C

 

 

 

18 to 29°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless type

 

 

18 to 30°C

 

 

 

16 to 30°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2) The set point temperature in heating operation can be offset

 

 

 

 

using item code (DN) 06.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

 

 

 

0

 

2

 

4

 

6

 

Heating suction temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp. correction

 

 

+0°C

 

+2°C

+4°C

 

+6°C

 

shift

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Automatic

(1) The difference between the temperature reading taken from

 

 

capacity

 

the Ta (room) sensor and the Ts (set point) selected on the

 

 

control

 

remote controller is used to determine the demand frequency

 

 

 

 

to the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Air volume

(1) The remote controller is used to select the modes “HIGH

HH > H+ > H >

 

control

 

(HH)”, “MED (M)”, “LOW (L)” or “AUTO”.

 

 

 

 

L+ > L > LL

 

 

(2) The difference between the temperature reading taken from

 

 

 

 

the Ta (room) sensor and the Ts (set point) selected is used

 

 

 

 

to control the air volume setting when in “AUTO” mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

Page 60
Image 60