7-2-2-3. Snowfall Fan Control

Header outdoor unit interface P.C. board

 

 

 

CN509 (4P BLK)

 

 

 

 

 

Connection cable

 

 

 

 

 

External master

 

PJ17

(4P WHI)

ON/OFF

 

 

 

 

 

 

 

control board

 

 

 

 

 

 

 

 

HEAT COOL

COM

SMC

Procured locally (Snow sensor)

Operation

The outdoor unit fan operates when a Snowfall signal is received.

Terminal

Input signal

Operation

 

ON

Snowfall fan control

 

 

 

OFF

(Operates outdoor unit fan.)

 

 

COOL

 

 

(SMC)

 

 

 

ON

Usual operation

 

 

 

OFF

(Releases control.)

 

 

The control contents are accepted during leading and trailing of the input signal.

(The status of leading and trailing should be held for 100mm. sec. or more.)

External master ON/OFF control board : TCB-PCMO 2E

Outdoor unit destination to be connected becomes the header outdoor unit (U1).

SMC: Snowfall detection switch

7-2-2-4. External master ON/OFF control

Header outdoor unit interface P.C. board

 

 

 

CN512 (4P BLU)

 

 

 

 

 

Connection cable

 

 

 

 

 

External master

 

PJ17

(4P WHI)

ON/OFF

 

 

 

 

 

 

 

control board

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

 

 

 

COM

 

 

 

 

 

SMC

SMH

Procured locally

Operation

The outdoor unit starts or stops the system.

Terminal

Input signal

Operation

 

 

 

 

 

 

 

 

 

 

 

 

COOL

ON

 

 

 

Starts collectively indoor units.

 

 

 

 

 

(SMC)

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat

ON

 

 

 

Stops collectively indoor units.

 

 

 

 

 

(SMH)

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The control contents are accepted during trailing of the input signal. (The status of trailing should be held for 100mm. sec. or more.)

NOTES

1)Do not turn on COOL and HEAT terminals concurrently.

2)Be sure to prepare a contact for each terminal. Outside signal: No voltage pulse contact

External master ON/OFF control board : TCB-PCMO 2E

Outdoor unit destination to be connected becomes the header outdoor unit (U1).

SMC: Input signal for start.

SMH: Input signal for stop.