13-2. How to Operate the System During Repair of the Malfunctioning Outdoor Unit

Procedure

1.Follow the aforementioned 13-1. Refrigerant Recovery in the Malfunctioning Outdoor Unit”.

2.Recover the refrigerant in the system by using a recovery device.

The refrigerant amount to be recovered is determined based upon the capacity of the malfunctioning outdoor unit (see the following table).

Example) In a case of backup for 10 hp-outdoor unit in 30 hp system: in the original system hp (30 hp system) = 37.5 kg

Refrigerant amount in system hp (20 hp system) after backup = 28.0 kg

Refrigerant amount to be recovered = 37.5 – 28.0 = 9.5 kg

3.For the unit which the refrigerant has been recovered, execute “Outdoor Unit Backup Setup” of another section.

System

 

Combination of outdoor units

Refrigerant amount

HP

 

(kg)

 

 

 

 

 

 

 

 

 

 

 

 

8

8

 

 

 

 

13.5

 

 

 

 

 

 

 

10

10

 

 

 

 

14.0

 

 

 

 

 

 

 

12

12

 

 

 

 

14.5

 

 

 

 

 

 

 

16

8

 

8

 

 

21.5

 

 

 

 

 

 

 

18

10

 

8

 

 

23.0

 

 

 

 

 

 

 

20

10

 

10

 

 

25.0

 

 

 

 

 

 

 

24

8

 

8

8

 

30.0

 

 

 

 

 

 

 

26

10

 

8

8

 

31.5

 

 

 

 

 

 

 

28

10

 

10

8

 

33.0

 

 

 

 

 

 

 

30

10

 

10

10

 

34.5

 

 

 

 

 

 

 

195

Page 195
Image 195
Toshiba MMU-AP0091H service manual 195, Refrigerant amount to be recovered = 37.5 28.0 = 9.5 kg