Functional part name

 

Functional outline

 

 

 

Pressure

High pressure sensor

(Connector CN501: Red)

sensor

 

1) Detects high pressure and uses it to control the capacity of the compressor.

 

 

2)

Detects high pressure during all cooling operation and uses it to control the fan when cooling

 

 

 

with low outside air.

 

 

3)

Detects under-cool of the indoor unit of which heating thermo.-ON during all heating operation

 

 

 

and simultaneous operation.

 

 

4)

Controls outdoor fan rpm during mainly cooling, part heating operation.

 

 

 

 

Low pressure sensor

(Connector CN500: White)

 

 

1)

Detects low pressure and uses it to control capacity of the compressor during all cooling

 

 

 

operation and simultaneous operation

 

 

2)

Detects low pressure and uses it to controls super heat during all heating operation and

 

 

 

simultaneous operation

 

 

 

Heater

Compressor case heater

(Compressor 1 Connector CN316: White, Compressor 2 Connector CN315: Blue)

 

 

1)

Prevents liquid accumulation in the compressor

 

 

 

 

Accumulator case heater

(Connector CN321: Red)

 

 

1)

Prevents liquid accumulation to accumulator

 

 

 

Balance pipe

1) Oil balancing pipe between outdoor unit (This unit does not use this Balance pipe.)

 

 

 

 

Operation mode

 

 

Operation mode

Outline

 

 

 

 

1.

All Indoor Unit(s)

Only cooling operation without heating operation

 

 

Operating for Cooling

Outdoor heat exchanger (Main heat exchanger) is used as a condenser.

 

 

 

 

2.

All Indoor Unit(s)

Only heating operation without cooling operation

 

 

Operating for Heating

Outdoor heat exchanger (Main heat exchanger) is used as an evaporator.

 

 

 

 

3.

Simultaneous operation

MIU for simultaneous operation

 

 

 

 

 

 

3-1. Mainly cooling, partly

Cooling/heating simultaneous operation with subjective cooling operation

 

 

heating operation

Outdoor heat exchanger (Sub heat exchanger) is used as a condenser.

 

 

 

 

 

 

3-2. Mainly heating, partly

Cooling/heating simultaneous operation with subjective heating operation

 

 

cooling operation

Outdoor heat exchanger (Main heat exchanger) is used as an evaporator.

 

 

 

 

4.

Defrost

Using the reversing operation of the 4-way valve, ice on the outdoor heat exchanger is

 

 

 

dissolved within a single cooling cycle.

 

 

 

 

For details of operation mode, refer to page 53 to 59.

50

Page 50
Image 50
Toshiba MMU-AP0091H service manual Operation mode Outline