Check code

Check code name

Cause of operation

[H07] / [d7]

Low oil level protection

1. Valves of balance pipes closed.

(TCC-L / AI-NET)

 

2. Miscabling or misinstallation of TK1 to TK4 sensors

 

 

3.

TK1 to TK4 sensor error

 

 

4.

Gas leak or oil leak of all outdoor units

 

 

5.

Refrigerant stagnation of compressor case

 

 

6.

SV3A, 3B, 3D, 3C, 3E valve error

 

 

7.

Clogging of oil return circuit from oil separator

 

 

8.

Clogging of oil-equation circuit system

In some cases, it may be difficult to check for leakage or clogging of refrigerant in low ambient temperature condition. In this case, it may take longer for the system to warm up before commencing checks.

(Criteria: Discharge temperature of TD1 and TD2 are 60°C or higher)

(*1)

a) Leakage check for SV3A valve (for multiple outdoor unit system)

• Turn off the power supply, take off connector of SV3A valve, and then start a test operation after power-ON.

• Check the temperature change at secondary side of SV3A valve during operation

(1 in the figure on the next page).

• If temperature is increased, it is a leakage of SV3A valve.

Replace SV3A valve.

Are TK1, TK2, TK3, and

TK4 sensors connected correctly?

Is sensor fitted correctly or mis-installed.

YES

Are TK1 and TK2 sensors connected correctly?

Is sensor fitted correctly or mis-installed.

Are sensor characteristics normal?

YES

Check leakage of SV6 circuit.

Normal

NO

 

Correct miswiring.

 

 

( TK1: CN514, TK2: CN515 )

*

 

 

TK3: CN516, TK4: CN523

NO

 

 

 

Correct miswiring.

 

 

(TS1: CN504, TS2: CN522)

 

Characteristics-2

 

Sensor error ÆReplace

 

 

 

Abnormal

Replace defective parts.

b) Leakage check for SV3C valve

• Turn off the power supply, take off connector of SV3C valve, and then start a test operation after power-ON.

• After operation for several minutes, check temperature at secondary side of SV3C valve

(2 in the figure on the next page).

• If temperature is high (equivalent to discharge temperature TD), it is a leakage of SV3C valve.

Replace SV3C valve.

(Even if there is leakage from SV3C valve does not occur, temperature of SV3C valve at secondary side

rises during operation. When the checked temperature is equivalent to TD temperature, it is a leakage of

SV3C valve. Replace SV3C valve.)

c) Clogging check for SV3B valve (for multiple outdoor unit system)

148

Check setup of cooling only

Abnormal

 

Set up cooling only operation mode.

 

 

Item code (DN) OF

indoor units is correct.

 

 

 

 

Cooling only operation mode: 0001

 

 

 

 

 

Normal

NO

 

 

Are characteristics of TK1 to TK4 normal?

 

 

 

Sensor error ÆReplace

 

 

 

*Characteristics-4

 

 

YES

 

 

 

 

 

 

 

 

 

 

Check gas leak of outdoor unit.

 

 

 

Abnormal

 

Determine position where

 

 

 

 

 

 

 

gas leaked and repair.

 

 

 

 

 

(Check oil leak at the outdoor unit.)

 

 

 

 

 

 

 

(Recharge, refill oil.)

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

Is the flow selector unit normal?

 

 

 

 

 

 

Repair the flow selector unit.

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check accumulation of

NO

 

 

 

(*1) Check leakage of

 

YES

 

 

 

 

 

solenoid valve. (SV3C)

 

 

 

Replace defective parts

refrigerant in compressor case.

 

 

 

 

Check clogging.

 

 

 

 

Refrigerant accumulation

 

 

 

(SV3E)

 

 

 

 

 

 

 

 

 

No leakage or clogging

 

 

 

 

 

 

 

 

Correct accumulation of

 

 

 

 

 

 

 

 

 

 

refrigerant in compressor case,

 

 

 

 

 

 

 

 

 

 

resetstartpoweroperation.supply and

 

 

 

 

(*2) Check clogging in oil

 

YES

 

 

 

 

 

 

 

 

recovery circuit of the oil separator.

 

 

 

Replace defective parts

 

 

 

 

 

 

 

(Capillary, Strainer)

 

 

 

 

 

 

 

 

 

 

 

Check clogging of SV3D valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check oil level judgment

 

 

 

 

 

No clogging

 

 

 

 

of each compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW01/02/03=1/16/1

are

 

 

 

 

 

 

 

displayed on 7-

segment display.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are all the oil levels appropriate?

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

Clogging

 

 

 

 

 

 

Check clogging of

 

 

Eliminate cause of stagnation.

 

 

 

 

oil-equalization circuit.

 

 

 

Replace defective parts

 

 

 

 

 

 

 

 

 

(*3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor/outdoor PMV error (Cause of refrigerant stagnation) Discharge check valve error, etc.

While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr], and push SW04

 

for 2 seconds or more, [Hr] [2] is displayed.

Set up SW02 = [9], and turn on SV3A, SV3B, SV3C valves (7-segment display [Hr] [ 3-]).

While outdoor unit is operating, check temperature change at secondary side of SV3B valve

 

(3 in the figure on the next page).

 

• If temperature does not rise (equivalent to suction temperature), it is a clogging of SV3B valve.

 

Replace SV3B valve.

d) Clogging check for SV3E valve

While the outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] the 7-segment display A displays [Hr],

 

and push SW04 for 2 seconds or more, [Hr] [ 2] is displayed.

Set up SW02 = [10], and turn on SV3E valve (7-segment displays [Hr] [ ]).

After operating for several minutes, check the pipe temperature at the secondary side of the SV3E valve.

 

If it is the equivalent to the outside temperature, SV3E valve may be clogged.

 

Replace SV3E valve.

• Note: If SV3E valve is clogged, the temperature of all TK1 to TK4 sensors do not change.

(*2) Clogging check for SV3D valve of oil return circuit from oil separator

a)Oil return circuit

While outdoor unit is operating, check temperature (secondary side of capillary) on oil return circuit (5 in the figure on the next page).

If temperature is equivalent to suction temperature, a clogging of strainer of oil return circuit or capillary is considered.

Repair the clogged part.

b)Clogging check for SV3D valve

While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr], and push SW04 for 2 seconds or more, [Hr] [2] is displayed.

Set up SW02 = [7], and turn on SV3D valve (7-segment display [Hr] [ 3d]).

If temperature is low at secondary side of the valve or it does not change, clogging of valve, capillary, or strainer is considered ( 6 in the figure on the next page).

(Note) When refrigerant stagnates in compressor shell, there may appear to be a low oil level.