Method 2

Before exchange, it is impossible to read out the setup contents due to EEPROM error.

Exchange of P.C. board for service & power ON: Procedure 2

ò

Writing-in of the setup data such as the model name, capacity code, indoor unit address high ceiling setup,

connection setup of option,

etc to EEPROM based upon customer’s information: Procedure 3

ò

Power supply reset (All the indoor units connected to the remote controller in case of group operation control)

Procedure 1 : Readout setup contents from EEPROM

(Contents of EEPROM with setup changed at local site include setup at shipment from the factory are read out.)

1.Push SET + CL + TEST buttons simultaneously for 4 seconds or more. 1

(Corresponds to number of the operation diagram of the remote controller in page 218.)

In a group operation control, the firstly displayed unit No. indicates the header indoor unit No.

In this case, ￿￿ is displayed in the item code (DN). The fan of the selected indoor unit operates, and also starts swinging in a model with flap.

2. Every pushing UNIT , the indoor unit Nos. in the group control are displayed successively. 2 (Corresponds to number of the operation diagram of the remote controller in page 218.)

Specify the indoor unit No. to be exchanged.

The fan of the selected indoor unit operates, and also starts swinging in a model with flap.

3.Using temperature setup / buttons, the item code (DN) can be moved up/down one by one. 3 (Corresponds to number of the operation diagram of the remote controller in page 218.)

4. First change the item code (DN) from ￿￿ ￿￿ . (Setup of filter sign lighting time)

In this time, make a note of contents of the displayed setup data.

5. In the next time, change the item code (DN) using / buttons. Make a note of contents of the setup data as same as the above.

6. Then repeat item 5., and make a note of contents of the important setup data as indicated in the attached

table (Example).

 

Item code necessary at minimum

The item code (DN) is consisted with ￿￿

to )) .

 

 

 

DN No. may jump on the way.

 

DN

Contents

 

7. When noting has finished, push TEST button to

10

Type

Type and capacity of

 

 

11

Indoor unit capacity

return to the normal stop status. 6

 

the indoor unit are

 

 

 

necessary to set up

 

12

Line address

(Corresponds to number of the operation diagram

the revolution

 

 

13

Indoor address

of the remote controller in page 218.)

 

frequency of the fan.

 

 

 

 

14

Group address

(It requires approx. 1 minute to operate the remote

 

 

 

 

controller.)

 

 

 

 

<Remote controller operation diagram>

SET DATA

UNIT No.

R.C. No.

TEMP.

3

 

5

FILTER

6

RESET TEST

 

1

 

 

 

ON / OFF

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

SET CL

UNIT

 

4

2

218

Page 218
Image 218
Toshiba MMU-AP0091H service manual Procedure 1 Readout setup contents from Eeprom, Remote controller operation diagram