Check code

Check code name

 

Cause of operation

 

 

 

[E31] / [CF]

IPDU communication error

1. Connection error of communication line

(TCC-L / AI-NET)

 

 

between IPDU and I/F P.C. board

 

 

2.

I/F P.C. board error

 

 

3.

IPDU P.C. board error

 

 

4.

External noise

 

 

 

 

Sub-code:

 

 

 

01: IPDU1 error

02: IPDU2 error

 

 

Check code

Check code name

Cause of operation

[F01] / [0F]

Indoor TCJ sensor error

TCJ sensor Open/Short

(TCC-L / AI-NET)

 

 

 

 

 

 

 

 

 

 

 

Is TCJ sensor connector (CN102: Red)

NO

 

 

 

 

 

Correct connection.

 

 

 

on indoor P.C. board normally connected?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03: IPDU1, 2 error

04: Fan IPDU error

05: IPDU1, fan IPDU error

06: IPDU2, fan IPDU error

07: All IPDU error or communication line error between IPDU-I/F P.C. boards, or outdoor I/F P.C. board error

If the fan IPDU is abnormal, be sure to check the voltage output on the fan power P.C. board.

Are characteristics of TCJ sensor resistance value normal?

YES

Check indoor main P.C. board.

Defect ÆReplace

NO

Replace TCJ sensor.

*Indoor unit temperature sensor characteristics See Characteristics-2.

143

Is jumper lead setup on the outdoor I/F P.C. board correct?

(Jumper 7, 8, 9 ON)

YES

Are communication connectors between I/F fan power P.C. board, and IPDU connected?

NO

Is there disconnection on communication line

between IPDU and I/F P.C. board?

NO

NO

Connect the jumper lead.

YES

Correct connection.

YES

Connect the communication line.

Check code

Check code name

Cause of operation

[F02] / [0d]

Indoor TC2 sensor error

TC2 sensor Open/Short

(TCC-L / AI-NET)

 

 

 

 

 

 

 

 

 

 

 

Is TC2 sensor connector (CN101: Black)

NO

 

 

 

 

 

Correct connection.

 

 

 

on indoor P.C. board normally connected?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there voltage between pin 4 and pin 5 of CN600 on I/F P.C. board? (Measure with tester: DC0 to 5 V)

YES

Is there voltage deflection between pin 3 and pin 5 of CN600 on I/F P.C. board? (Measure with tester: DC 0 to 5V, 5 pin GND)

YES

NO

I/F P.C. board error

NO

IPDU P.C. board error

Are characteristics of TC2 sensor

resistance value normal? *

YES

Check indoor main P.C. board.

Defect ÆReplace

NO*

Replace TC2 sensor.

Indoor unit temperature sensor characteristics

See Characteristics-2.

On the fan power supply P.C. board, 1) CN503: Between pins 1 and 5 12V

2)CN503: Between pins 2 and 5 Æ7V

3)Between +5V and GND of CN505: 5V

YES

Replace P.C. board according to auxiliary code.

NO

Replace fan power P.C. board.

Auxiliary code

P.C. board to be replaced

01

IPDU1

02

IPDU2

 

 

03

IPDU1, 2

Check code

Check code name

Cause of operation

[F03] / [93]

Indoor TC1 sensor error

TC1 sensor Open/Short

(TCC-L / AI-NET)

 

 

 

 

 

 

 

 

 

 

 

Is TC1 sensor connector (CN100: Brown)

NO

 

 

 

 

 

Correct connection.

 

 

 

on indoor P.C. board normally connected?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

Fan IPDU

05

IPDU1, fan IPDU

 

 

06

IPDU2, fan IPDU

 

 

07

IPDU1, 2, fan IPDU, I/F

Are characteristics of TC1 sensor

resistance value normal? *

YES

Check indoor main P.C. board.

Defect ÆReplace

NO

Replace TC1 sensor.

*Indoor unit temperature sensor characteristics See Characteristics-2.