131

 

 

 

Check code

 

 

 

 

 

 

 

 

 

 

 

 

Detected

 

 

 

 

 

 

Main

 

Outdoor 7-segment display

AI-NET

Check code name

Status

Error detection condition

 

Check item (position)

 

 

position

 

 

remote

 

 

central control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller

Check code

Sub-code

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L06

L06

No. of indoor units with priority

96

I/F

Duplicated indoor units with

All stop

Indoor units with priority were

Check display of indoor unit with priority and outdoor unit.

 

 

 

 

 

 

priority

 

duplicated.

 

 

 

 

 

 

 

 

(Displayed on the unit other

 

 

 

 

 

 

 

 

 

 

than indoor unit with priority)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L07

99

Indoor

Group line in individual

Corresponding

At least one indoor unit connected

Check indoor address.

 

 

 

 

 

 

indoor unit.

unit only stops. to a group existed in the individual

 

 

 

 

 

 

 

 

 

 

indoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L08

L08

99

Indoor

Indoor group / address

Corresponding

Address was not yet set up.

Check indoor address.

 

 

 

 

 

 

unset

unit only stops.

 

Note)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After installation, this code is displayed when the power is first

 

 

 

 

 

 

 

 

 

turned on.

 

 

 

 

 

 

 

 

 

 

 

L09

46

Indoor

Indoor capacity unset

Corresponding

Indoor unit capacity was unset.

Set up indoor capacity. (DN=11)

 

 

 

 

 

 

 

unit only stops.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L10

L10

88

I/F

Outdoor capacity unset

All stop

On the I/F P.C. board for service,

Check model setup on outdoor I/F P.C. board A’ssy for service.

 

 

 

 

 

 

 

 

jumper line was not cut according to

 

 

 

 

 

 

 

 

 

 

the model.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L17

L17

 

I/F

Inconsistent models of

 

1 and 2 series outdoor units have

Check outdoor units.

 

 

 

 

 

 

outdoor units

 

been mixed.

 

 

 

 

 

 

 

 

 

 

 

 

 

L18

L18

Corresponding indoor address

8A

I/F

FS unit system error

Corresponding

An indoor unit which is not

• Check setup of remote controller (DN=[OFF]).

 

 

 

 

 

 

 

unit only stops. connected with a FS unit is

Check FS unit.

 

 

 

 

 

 

 

 

operating without setup of cooling

 

Check pipe connection to FS unit.

 

 

 

 

 

 

 

 

only mode.

 

 

 

 

 

 

 

 

 

 

(Mispiping between discharge gas and suction gas)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check miswiring/misinstallation of SVS/SVD valves.

 

 

 

 

 

 

 

 

 

 

 

L20

98

AI-NET,

Duplicated central control

All stop

Duplicated central control

• Check central control address.

 

 

 

 

 

Indoor

addresses

 

addresses

• Check network adaptor P.C. board. (In case of AI-NET)

 

 

 

 

 

 

 

 

 

 

 

L28

L28

46

I/F

Quantity over of connected

All stop

There were more than four outdoor

• Check No. of connected outdoor units.

 

 

 

 

 

 

outdoor units

 

units.

 

(Max. 4 units per 1 system)

 

 

 

 

 

 

 

 

 

Check communication line between outdoor units.

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

L29

L29

01: IPDU1 error

CF

I/F

IPDU quantity error

All stop

No. of IPDU units detected when

• Check model setup for outdoor I/F service P.C. board.

 

 

 

02: IPDU2 error

 

 

 

 

power was turned on were less.

• Check connection of UART communication connector.

 

 

 

03: IPDU1, 2 errors

 

 

 

 

 

Check IPDU, fan IPDU, and I/F P.C. board error.

 

 

 

04: Fan IPDU error

 

 

 

 

 

Note)

 

 

 

05: IPDU1 + Fan IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

UART: Universal Asynchronous Receiver Transmitter

 

 

 

06: IPDU2 + Fan IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07:All IPDU error or communication error between IPDU and I/F P.C. board, or outdoor I/F P.C. board error

L30

L30

Detected indoor address

b6

Indoor

Interlock in indoor unit from

Corresponding

• Outside error input terminal

n Outside device is connected to connector (CN80):

 

 

 

 

 

outside

unit only stops.

Detected signal to (CN80) for

1)

Check outside device error.

 

 

 

 

 

 

 

more than 1 minute

2)

Check indoor P.C. board error.

 

 

 

 

 

 

 

 

n Outside device is not connected to connector (CN80):

 

 

 

 

 

 

 

 

1)

Check indoor P.C. board error.

 

 

 

 

 

 

 

 

 

L31

I/F

Extended IC (Integrated

Operation

P.C. board (I/F) parts error

Check indoor (I/F) P.C. board.

 

 

 

 

 

Circuit) error

continues.

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 131
Image 131
Toshiba MMU-AP0091H 131, Check code Detected Main Outdoor 7-segment display, Remote Central control Controller Check code