6.Fully close the service valve in the gas pipe of the malfunctioning outdoor unit approximately 10 minutes after the system has started.

7.Push SW04 of the malfunctioning outdoor unit, to display the pressure data (MPa).

For each successive push of SW04, the data display changes as shown in the example below.

Display Example

[rd] [ 11]

 

[Pd] [1.20]

 

[Ps] [1.20]

 

 

Initial display

 

High pressure

 

Low pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Select an outdoor unit for pressure adjustment as follows]

8.When operating the pump down mode, the outdoor unit which has the lowest unit number is selected as the outdoor unit for the pressure adjustment.

Unit No.

When SW01/02/03 are set to 1/1/1, the number displayed on the 7-segment display indicates the unit number ([U#][---]: # indicates the unit number)

[Set up all other outdoor units as follows]

9.Fully close the service valves of all the other outdoor unit balance pipes. Only keep the service valves of the balance pipes of the unit in which the pressure adjustment will be made and the malfunctioning unit fully open.

[Setup for outdoor unit for adjustment of pressure]

10.Set up the rotary SW01/02/03 to 1/2/2 on the interface P.C. board of the outdoor unit in which the pressure adjustment will be made.

11.The low pressure (Ps) data is displayed on the 7-segment display.

Slowly close the service valve of the gas pipe and adjust so that a pressure of 0.12 MPa is displayed.

12.When the low pressure (Ps) of the malfunctioning outdoor unit is almost the same as that of the unit in which the pressure adjustment has been made, fully close the service valve of the gas pipe in the unit which the pressure adjustment was made.

[Set up the malfunctioning outdoor unit as follows]

13.When the pressure of the malfunctioning outdoor unit is below 0.1 MPa, fully close the service valve of the balance pipe and push SW05 on the interface P.C. board to finish the pump down operation.

14.Turn off the power supplies to all of the outdoor units and use a refrigerant recovery device to recover the remaining refrigerant in the outdoor unit, in which the pump down operation has been completed. Be sure to measure the recovered refrigerant, as the same amount of refrigerant will be required to be recharged after the repair.

9

6

 

 

Fully close the balance pipes of

Fully close the service valve of

the outdoor units except the

the gas pipe approx. 10 minutes

unit for pressure adjustment

after the system has started.

and unit with the malfunction.

 

 

 

 

 

 

 

 

Malfunctioning outdoor unit

 

 

 

 

 

 

 

 

7

 

 

 

 

The low pressure

 

 

 

 

is displayed by

 

 

 

 

pushing SW04.

 

 

 

 

[Ps] [###]

 

 

 

 

 

 

 

8

The lowest number outdoor unit is selected as the outdoor unit for pressure adjustment.

10

The low pressure is displayed by setting SW01/02/03 to 1/2/2. [Ps] [###]

13

When low pressure of the malfunctioning outdoor unit is below 0.10 MPa, fully close the service valve of the balance pipe.

14

Turn off the power of all the outdoor units. Using a recovery device, reclaim the remaining refrigerant in the outdoor unit in which pump-down operation has finished and measure the amount.

11

Close service valve of the gas pipe gradually while checking the low pressure, and then adjust the pressure to 0.12 MPa.

12

When low pressure of the malfunctioning outdoor unit and low pressure of the outdoor unit for pressure adjustment becomes almost same, fully close the service valve of gas pipe on the outdoor unit for pressure adjustment

Return all rotary switches SW01/02/03 to 1/1/1.

192

Page 192
Image 192
Toshiba MMU-AP0091H Select an outdoor unit for pressure adjustment as follows, Set up all other outdoor units as follows