• Check connector/terminal connection on IPDU P.C. board.
• Check conduction of case heater.
(Check activation error due to liquid stagnation in compressor.)
• Check outdoor P.C. board (IPDU) error.
• Check outdoor MG-SW or OCR.
MG-SW : Magnet Switch, OCR : Over-current Relay

127

 

 

Check code

 

 

 

 

 

 

 

 

 

 

 

Detected

Check code name

Status

Error detection condition

 

Check item (position)

Main

Outdoor 7-segment display

AI-NET

 

position

 

remote

 

 

central control

 

 

 

 

 

controller

Check code

Sub-code

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F13

F13

01: Compressor 1 side

43

IPDU

TH sensor error

All stop

• Resistance value of sensor is

IGBT built-in temp sensor error

 

 

02: Compressor 2 side

 

 

 

 

infinite or zero (Open/Short).

 

Exchange IPDU P.C. board.

 

 

 

 

 

 

 

 

 

 

F15

F15

18

I/F

Outdoor temp sensor

All stop

During operation of

Check installation of TE1 sensor and TL sensor.

 

 

 

 

 

miscabling (TE1, TL)

 

compressor in HEAT mode, the

Check characteristics of TE1 and TL sensor resistance value.

 

 

 

 

 

 

 

TE1 detection temp was higher

Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

than that of TL by the specified

 

 

 

 

 

 

 

 

 

value continued for 3 minutes

 

 

 

 

 

 

 

 

 

or more.

 

 

 

 

 

 

 

 

 

 

 

F16

F16

43

I/F

Outdoor pressure

All stop

High-pressure Pd sensor and

• Check connection of high-pressure Pd sensor connector.

 

 

 

 

 

sensor miscabling

 

low-pressure Ps sensor were

Check connection of low-pressure Ps sensor connector.

 

 

 

 

 

(Pd, Ps)

 

exchanged, or output voltages

• Check pressure sensors Pd and Ps error.

 

 

 

 

 

 

 

of both sensors are zero.

 

 

 

 

 

 

 

Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check compression error of compressor.

 

 

 

 

 

 

 

 

 

 

F23

F23

43

I/F

Ps sensor error

All stop

Output voltage of Ps sensor

Misconnection of Ps sensor and Pd sensor connectors

 

 

 

 

 

 

 

was zero.

Check connection of Ps sensor connector.

 

 

 

 

 

 

 

 

Check Ps sensor error.

 

 

 

 

 

 

 

 

Check compression error of compressor.

 

 

 

 

 

 

 

 

Check 4-way valve error.

 

 

 

 

 

 

 

 

Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

Check SV4 circuit error.

 

 

 

 

 

 

 

 

 

 

F24

F24

43

I/F

Pd sensor error

All stop

Output voltage of Pd sensor

Check connection of Pd sensor connector.

 

 

 

 

 

 

 

was zero. (Sensor Open)

Check Pd sensor error.

 

 

 

 

 

 

 

Pd > 4.15MPa during stop of

Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

compressor

 

 

 

 

 

 

 

 

 

 

 

 

F29

12

Indoor

Indoor other error

Corresponding

Indoor P.C. board did not

Check indoor P.C. board error (EEPROM error).

 

 

 

 

 

 

unit only stops.

operate normally.

 

 

 

 

 

 

 

 

 

 

 

F31

F31

1C

I/F

Outdoor EEPROM error

All stop (*1)

Outdoor P.C. board (I/F) did not

• Check power voltage.

 

 

 

 

 

 

 

operate normally.

Check power noise.

 

 

 

 

 

 

 

 

Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

 

 

 

H01

H01

01: Compressor 1 side

1F

IPDU

Compressor breakdown

All stop

Inverter current detection circuit

Check power voltage. (AC220–240V ± 10%).

 

 

02: Compressor 2 side

 

 

 

 

detected over-current and

Check compressor error.

 

 

 

 

 

 

 

stopped.

Check cause of abnormal overload operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor P.C. board (IPDU) error.

 

 

 

 

 

 

 

 

 

 

H02

H02

01: Compressor 1 side

1d

IPDU

Compressor error (lock)

All stop

Over-current was detected

Check compressor error.

 

 

02: Compressor 2 side

 

 

MG-SW error

 

several seconds after header

• Check power voltage. (AC380–10%, 415V +10%).

 

 

 

 

 

OCR operation

 

compressor had started.

• Check cable of compressor and phase-missing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*1) All stop only in case of the header unit The follower unit continues operation.

Page 127
Image 127