7-2-2. Applied Control in Outdoor Unit

The following functions are available by using a separately supplied P.C. board.

Set up the switches on the outdoor unit (U1).

No.

Function

Switch No.

Bit

Connector No.

Used control P.C. board

 

 

 

 

 

 

1

Power peak-cut control (Standard)

SW07

1

CN513

TCB-PCDM2E

 

 

 

 

 

 

2

Power peak-cut control (Expansion)

SW07

1,2

CN513

TCB-PCDM2E

 

 

 

 

 

 

3

Snowfall fan control

CN509

TCB-PCMO2E

 

 

 

 

 

 

4

External master ON/OFF control

CN512

TCB-PCMO2E

 

 

 

 

 

 

5

Night operation control

CN508

TCB-PCMO2E

 

 

 

 

 

 

6

Operation mode selection control

CN510

TCB-PCMO2E

 

 

 

 

 

 

Outdoor unit interface P.C. board

Connector position detail

 

 

CN508

CN509

CN510

CN513

 

Red

Black

White

Blue

CN511

Green

Switch position detail

SW07

Bit 1 For power peak-cut control selection

Bit 2 For power peak-cut control (expansion) selection