Toshiba MMU-AP0091H 161, P26 Tr short-circuit protection error, P29 Compressor position, P31

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 161
Image 161

Check code

Check code name

Cause of operation

[P26] / [14]

G-Tr short-circuit protection error 1.

Outdoor unit power error

(TCC-L / AI-NET)

2.

IPDU error/Cable connection error

 

3.

Compressor error

 

4.

IPDU P.C. board error

Check code

Check code name

Cause of operation

[P29] / [16]

Compressor position

1.

Wire connection error.

(TCC-L / AI-NET)

detective circuit error

2.

Compressor error

 

 

3.

IPDU P.C. board error

Sub-code:01: Compressor 1 side 02: Compressor 2 side

Sub-code:01: Compressor 1 side 02: Compressor 2 side

Is the power supply voltage

NO

to the outdoor unit normal?

 

 

YES

 

 

 

 

 

NO

Is wire connector connection

 

on the IPDU P.C. board normal?

 

 

YES

 

 

 

 

 

NO

Is compressor operation normal?

 

 

 

YES

 

 

 

 

 

NO

Is smoothing condenser normal?

 

(1500µF, 350V)

 

Correct power line.

Correct the wire connections.

Replace compressor.

Check capacity valve external appearance.

Are the connectors and wiring

NO

 

to the compressor normal?

 

 

YES

 

 

 

 

 

YES

Is it grounded?

 

 

 

NO

 

 

 

 

 

YES

Is there a winding short?

 

(Is winding resistance 0.1 to 0.3W?)

 

 

NO

 

 

 

 

 

 

YES

Is the winding open circuit?

NO

Check and correct circuit and

wires, i.e. to the compressor, etc.

Compressor error ÆReplace

Compressor error ÆReplace

Compressor error ÆReplace

161

YES

Replace IPDU P.C. board.

Check IPDU P.C. board.

Failure ÆReplace

Check code

Check code name

Cause of operation

 

 

 

[P31] / [47]

Other indoor error

Other indoor unit in the group has a error.

(TCC-L / AI-NET)

(Group follower unit error)

 

 

 

 

When the header unit of the group detects [E03, L03, L07, L08 error], the follower unit(s) in the group display [P31] error and stop. There are no check code displays or alarm record on the main remote controller.

Page 161
Image 161
Toshiba MMU-AP0091H 161, P26 Tr short-circuit protection error, P29 Compressor position, Detective circuit error, P31