Check code

 

 

Check code name

 

 

Cause of operation

 

 

 

 

 

[F31] / [1C]

 

Outdoor EEPROM error

1.

Outdoor unit power error (Voltage, noise, etc.)

(TCC-L / AI-NET)

 

 

 

2.

Outdoor I/F P.C. board error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there any trouble of

 

YES

 

 

 

Check power voltage and line.

 

 

 

 

 

Correct power line.

outdoor unit power supply?

 

 

 

 

 

 

 

 

 

 

Check external noise, etc.

 

 

 

 

 

 

 

Check code

Check code name

Cause of operation

[H02] / [1d]

Compressor error (Lock)

1. Outdoor unit power line error

(TCC-L / AI-NET)

 

2.

Compressor circuit system error

 

 

3.

Compressor error

 

 

4.

Refrigerant stagnation in compressor shell

 

 

5.

IPDU P.C. board error

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check I/F P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check code

 

Check code name

 

Cause of operation

 

 

 

[H01] / [1F]

Compressor breakdown

1. Outdoor unit power line error

(TCC-L / AI-NET)

 

 

2. Compressor circuit system error

 

 

 

 

3.

Compressor error

 

 

 

 

4.

Cause of abnormal overload operation

 

 

 

 

5.

IPDU P.C. board error

 

 

 

 

 

 

 

Sub-code:01: Compressor 1 side

Is power voltage of

outdoor unit normal? 1

YES

Does voltage drop occur

when other compressor starts?

NO

Does OCR of MG-SW operate?

NO

02: Compressor 2 side

NO

1 380 – 415V ± 10%

YES

YES

Correct power line.

Reset OCR manually. 3

146

Sub-code:01: Compressor 1 side 02: Compressor 2 side

NO

Is power voltage of outdoor unit normal?

380 – 415V ± 10%

YES

Is wiring or connector connection

on IPDU P.C. board normal?

YES

Is not it an abnormal overload?

NO

NO

YES

Correct connector connection

or wiring.

Correct cause of overload.

Does voltage drop occur

YES

 

Correct power line.

 

when other compressor starts?

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

Is connection of wiring or connection of

NO

 

 

 

Correct connector connection or wiring.

 

 

connector on IPDU P.C. board normal?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Is winding resistance

 

 

 

 

NO

 

Compressor error

 

between phases of corresponding

 

 

 

 

 

 

 

(Motor burning, etc.)

 

compressor normal? (Note 1)

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

Is not it an abnormal overload?

 

Correct cause of overload.

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

Take off lead cable of compressor.

 

 

 

 

 

 

 

 

1. Check resistance between windings:

 

C

 

 

It is normal if there are 0.7 to 0.9 .

S

2.Check insulation between outdoor cabinet and terminal:

It is normal if there are 10M or more.

Check IPDU P.C. board.

Note 1

R

*After checking the output, when connecting the compressor lead again to the compressor terminal, check surely there is no distortion on the Fasten receptacle terminal.

If it is loosened, caulk it with pinchers, etc and then connect

Details of compressor

lead to the terminal firmly.

power connecting section

Is there no refrigerant stagnation

 

YES

YES

 

Correct refrigerant stagnation

 

 

 

Is case heater output normal?

 

 

 

in compressor shell?

 

 

 

 

 

in compressor shell.

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation starts.

 

 

 

Check case heater.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

Is compressor normal? 2

 

 

 

Compressor error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

2 Check the following items mainly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Existence of abnormal sound and abnormal vibration during operation or starting

 

 

 

 

 

 

Check IPDU P.C. board.

 

2. Abnormal overheat of case during operation or stop time (Never touch with hands.)

3.Current of compressor lead during operation or starting time (No varied change of current) change

3 If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (T02) of Comp-IPDU is correct or not.

Check code

Check code name

 

 

Cause of operation

 

 

 

[H03] / [17]

Current detective

1. Cabling or connector connection error on IPDU P.C. board

(TCC-L / AI-NET)

circuit system error

2. IPDU P.C. board error

 

 

 

Sub-code:01: Compressor 1 side 02: Compressor 2 side

Wiring or connector connection

NO

 

 

 

 

 

Correct connector connection or cabling.

 

 

 

on IPDU P.C. board normal?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check IPDU P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

Page 146
Image 146
Toshiba MMU-AP0091H service manual F31 / 1C, H02 / 1d Compressor error Lock, H01 / 1F, 146, H03