nLeaving-ON prevention control

[Function]

This function controls the indoor units individually. It is connected with cable to the control P.C. board of the indoor unit.

• In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code - is set to the connected indoor unit.

It is used when the start operation from outside if unnecessary but the stop operation is necessary.

Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected.

When inserting a card, start/stop operation from the remote controller is allowed.

When taking out a card, the system stops if the indoor unit is operating and start/stop operation from the remote controller is forbidden.

(1) Control items

1) Outside contact ON : The start/stop operation from the remote controller is allowed. (Status that card is inserted in the card switch box)

2)Outside contact OFF : If the indoor unit is operating, it is stopped forcedly. (Start/Stop prohibited to remote controller)

(Status that card is taken out from the card switch box)

When the card switch box does not perform the above contact operation, convert it using a relay with b contact.

(2)Operation

1

2

3

4

5

Handle the wired remote controller switch in the following procedure.

Use the wired remote controller switch during stop of the system.

Push concurrently SET

+ CL

+ TEST buttons for 4 seconds or more.

Using the setup temp

 

or

button, specify the item code - .

Using the timer time

or

 

button, set ￿￿￿￿ to the setup data.

Push SET

button.

 

 

 

Push TEST

button. (The status returns to the usual stop status.)

(3) Wiring

 

 

 

 

Relay (procured locally)

CN61

 

 

 

 

T10

 

1

1

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

(YEL)

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

* In the figure, the contact indicates

 

 

 

 

 

 

 

 

 

 

 

 

4

4

 

 

 

 

 

 

 

 

 

 

 

 

 

a status that the card is taken out.

 

 

 

5

5

 

 

 

 

 

 

 

 

 

 

6

6

 

 

 

 

 

 

 

Indoor control P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside contact (Card switch box, etc: Procured locally)

Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.

nDemand control from indoor unit

When the relay is turned on, a forced thermostat-OFF operation starts.

• Wiring example

CN73

 

 

 

1

1

 

 

 

EXCT

2

2

 

 

 

 

 

(2P plug: RED)

Relay (procured locally)

Note) Determine the cable length between the indoor or outdoor control P.C. board and the relay within 2m.

Relay coil signal

Indoor control P.C. board

79

Page 79