No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

8

Recovery control

(1)

The indoor unit which stops operation, thermostat is OFF,

• Recovery operation is

 

for cooling

 

or operates in FAN mode opens PMV of the indoor unit by

usually executed every 2

 

refrigerant and oil

 

the specified opening degree when cooling refrigerant or oil

hours.

 

 

 

recovery signal is received from the outdoor unit.

 

 

 

(2)

Drain pump of 4-way air discharge cassette type and

 

 

 

 

concealed duct type operate during recovery control mode.

 

 

 

 

 

9

Recovery control

The indoor unit which stops operation, thermostat is OFF, or

• In the indoor unit which

 

for heating

operates in FAN mode performs the following controls when

thermostat is OFF, or

 

refrigerant and oil

the heating refrigerant/Oil recovery signal is received from the

operates in FAN mode,

 

 

outdoor unit.

“ ” lamp goes on.

 

 

1) Opens PMV of the indoor unit by the specified opening

• Recovery operation is

 

 

 

degree.

usually executed every

 

 

2) Stops the fan.

1 hour.

 

 

3)

Only 4-way Air Discharge Cassette type air conditioner

 

 

 

 

rotates the indoor fan with intermittent operation for

 

 

 

 

approximately 1 minute after recovery control.

 

 

 

4)

Only 4-way Air Discharge Cassette type air conditioner

 

 

 

 

rotates the indoor fan with intermittent operation for

 

 

 

 

approximately 1 minute after recovery control as the

 

 

 

 

outdoor unit.

 

 

 

5) After recovery control, drain pump of 4-way air discharge

 

 

 

 

cassette type and concealed duct type will operate.

 

 

 

 

 

 

10

Short intermittent

(1)

For 5 minutes after the operation has started, the operation

 

 

operation

 

is continued even if entering thermostat-OFF condition.

 

 

compensation

(2)

However, if the thermostat has been turned off by changing

 

 

control

 

the set up temp., the thermostat is OFF with even the

 

 

 

 

above condition. The protective control has priority.

 

 

 

 

 

 

11

Drain pump

(1)

During “COOL” operation (including DRY operation), the

Check code [P10]

 

control

 

drain pump operates.

 

 

 

(2)

While the drain pump operates, if the float switch works,

 

 

 

 

the drain pump continues operation and a check code is

 

 

 

 

displayed.

 

 

 

(3)

While the drain pump stops, if the float switch works, turn

 

 

 

 

off the capacity demand command, stop the operation, and

 

 

 

 

operate the drain pump. If the float switch continues

 

 

 

 

operating for approx. 5 minutes, the operation stops and

 

 

 

 

the check code is displayed.

 

 

 

(4)

In heating operation, if humidifier “provided” is judged,

 

 

 

 

compressor “ON”, compressor “ON”, fan “ON”, and MAX

 

 

 

 

(TC2, TCJ) > 33°C, the drain pump operates.

 

 

 

 

 

 

12

Elimination of

(1)

When the air conditioner stops in the “HEAT” mode, drive

 

 

remaining heat

 

the indoor fan with “LOW” mode for approx. 30 seconds.

 

 

 

 

 

 

13

Auto louver

(1)

When the louver signal has been received from the remote

 

 

control

 

controller, the louver operates if the indoor fan is operating.

 

 

 

(2)

In 4-way Air Discharge Cassette type, the discharge louver

 

 

 

 

automatically directs downward if the operation stops.

 

 

 

(3)

In 4-way Air Discharge Cassette type, the discharge louver

 

 

 

 

directs upward if the heating operation is being prepared.

 

 

 

 

 

 

14

Filter sign display

(1)

The operation time of the indoor fan is integrated and

 

 

(None in wireless

 

stored in memory, and the filter exchange signal is sent to

 

 

type)

 

the remote controller to display on the remote controller

 

 

Provided in the

 

LCD after the specified time.

 

 

separately laid

(2)

When the filter reset signal is received form the remote

 

 

type

 

controller, time of the integrated timer is cleared. In this

 

 

TCB-AX21E.

 

time, if the specified time has passed, the measured time is

 

 

 

 

reset and LCD display disappears.

 

 

 

 

 

 