To change all the indoor addresses from an arbitrary wired remote controller; (When the setup operation with automatic address has finished, this change is available.)

Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each same refrigerant line

Change the address in the address check/change mode. <Procedure> (Operation while air conditioner stops)

1Push the timer time + TEST buttons simultaneously for 4 seconds or more. Firstly, the line 1, item code AC (Address Change) is displayed.

2

Using

UNIT + SWING/FIX buttons, select the line address.

3

Push SET

button.

The indoor unit address, which is connected to the refrigerant pipe of the selected outdoor unit is dis- played and the fan is turned on.

First the current indoor address is displayed on the setup data. (Line address is not displayed.)

4 The indoor address of the setup data moves up/down by the timer time / buttons.

Change the setup data to a new address.

 

5

Push SET button to determine the setup data.

 

6

Every pushing

UNIT

button, the indoor unit numbers in the identical pipe are successively

 

 

 

 

displayed. Only fan of the selected indoor unit operates.

 

 

Repeat the procedure 4 to 6 and change all the indoor addresses so that they are not duplicated.

 

7

Push SET button.

 

 

 

 

(All the displays on LCD go on.)

92

8

Push TEST button to finish the procedure.

 

CODE No.

 

CODE No.

SET DATA SETTING

 

SET DATA SETTING

 

UNIT

No.

UNIT

No.

R.C.

No.

R.C.

No.

 

TEMP.

 

 

ON / OFF

 

TEMP.

 

 

ON / OFF

 

 

TIMER SET

FAN

MODE

4

 

TIMER SET

FAN

MODE

1

 

TIME

SWING/FIX

VENT

 

TIME

SWING/FIX

VENT

FILTER

 

 

2

FILTER

 

 

6

RESET TEST

SET CL

UNIT

8

RESET TEST

SET CL

UNIT

3

 

 

 

 

 

 

 

 

 

Cancel of line selection

 

5, 7 To finish the set

 

 

 

 

 

 

Here, if the unit No is not called up, the outdoor unit in

Operation procedure

 

1 2

3

4

Æ

this line does not exist.

CL

5 Æ6

Æ7

Æ8

 

procedurePush button,2 . and then select a line according to

End

Clearance of address (Return to status (Address undecided) at shipment from factory)

Method 1

An address is individually cleared from a wired remote controller.

“0099” is set up to line address, indoor address, and group address data from the remote controller.

(For the setup procedure, refer to the abovementioned address setup from the remote controller.)

Method 2

Clear the indoor addresses in the same refrigerant line from the outdoor unit.

1.Turn off the power of the refrigerant line to be returned to the status at shipment, and change the header unit to the following status.

1)Remove the relay connector between [U1U2] and [U3U4]. (If it has been already removed, leave it as it is.)

2)Turn on SW30-2 on the interface P.C. board of the header unit if it is OFF. (If it has been already ON, leave it as it is.)

Central control

device

U1 U2

U3 U4

Header unit

Follower unit

 

HeaderCent unitnit

Follower unit

 

HeaderCenter unitunit

 

U3 U4

U3 U4

U3 U4

U3 U4

U3 U4

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

 

U1 U2

 

U1 U2

 

U1 U2

 

U1 U2

 

A

B

A B

 

A

B

A B

 

A

B

Remote

Remote

 

Remote

 

 

Remote

controller

controller

 

controller

 

 

controller

Unit of which address is to be returned to the initial status

2.Turn on the indoor/outdoor power of which address is to be cleared. After approx. 1 minute, check that “U.1. - - -” is displayed, and then execute the following operation on the interface P.C. board of the header unit of which address is to be cleared in the refrigerant line.

SW01

SW02

SW03

SW04

Address which can be cleared

 

 

 

 

 

2

1

2

After checking that “A.d.buS” is displayed on 7-degment

Line + Indoor + Group address

display, and then push SW04 for 5 seconds or more.

 

 

 

 

 

 

 

 

 

2

2

2

After checking that “A.d.nEt” is displayed on 7-degment

Central address

display, and then push SW04 for 5 seconds or more.

 

 

 

 

 

 

 

 

 

3.After “A.d. c.L.” has been displayed on 7-degment display, return SW01/SW02/SW03 to 1/1/1.

4.When the address clearing has correctly finished, “U.1.L08” is displayed on 7-degment display after a while. If “A.d. n.G.” is displayed on 7-degment display, there is a possibility which is connected with the other refrigerant line. Check again the relay connector between [U1U2] and [U3U4] terminals.

NOTE) Be careful that the other refrigerant line address may be also cleared if clearing operation is not correctly executed.

5.After clearing of the address, set up an address again.

Page 92
Image 92
Toshiba MMU-AP0091H End, Push SET button to determine the setup data, Push Test button to finish the procedure, Method