• Check outdoor PMV clogging (PMV1, 2).
• Check characteristics of TD1, TD2 sensor resistance value.
• Check indoor air filter clogging.
• Check pipe clogging.
• Check SV4 circuit (Valve leakage, misinstallation)
• Check mispiping of discharge gas/suction gas main pipe.
• Check Flow selector unit.
Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.) Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors.
Check miswiring of SVS/SVD valves.
Discharge temperature TD1 or TD2 was continuously 108°C or higher for 10 minutes.
• Check Flow selector unit.
Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.)
Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring between FS unit and indoor unit, and connection of connectors.
Check miswiring of SVS/SVD valves.
• Check refrigerant shortage.
In heating operation: 40°C or higher
• Check leakage of SV5 circuit.
• Check mispiping of discharge gas/suction gas main pipe.
In cooling operation: 60°C or higher
• Check 4-way valve error.
• Check leakage of SV4 circuit.
TS error judgment standard temperature
• Check characteristics of TS1 sensor resistance value.
• Check outdoor PMV clogging (PMV1, 2).
• Check full open of outdoor service valves (gas side, liquid side).
• Check refrigerant shortage.
• Check TS1, TS2 sensor error.
• Check capillary clogging of oil return circuit from oil separator.
• Check outdoor P.C. board (I/F) error.
• Check clogging of 4-way valve error circuit.
Check item (position)
• Check Pd and Ps sensor error.
• Check full close operation of outdoor PMV (1, 2).
• Check indoor type code (DN=10) and the capacity code (DN=11).
• Check influence of outside air control.
• Check indoor P.C. board error.
• Check fan motor error.
• Check connection of fan connector and wiring.
• Check indoor P.C. board error.
• Check clogging of drain pipe.
• Check the drain pump circuit.
• Check operation of drain pump unit.
• Check the float switch connector.
• Check IPDU error.(IGBT built-in temp sensor (TH) error).
• Check fixation between IGBT and heat sink. (Check screwing and contact.)
• Check clogging of heat sink cooling duct.
• Check outdoor fan system error.
• Check power voltage.

 

 

 

Check code

 

 

 

 

 

 

 

 

 

 

 

 

Detected

Check code

 

 

 

 

 

Main

Outdoor 7-segment display

AI-NET

Status

Error detection condition

 

 

 

position

name

 

 

 

remote

 

 

central control

 

 

 

 

 

controller

Check code

Sub-code

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P07

P07

01: Compressor

1C

IPDU

Heat sink

All stop

IGBT built-in temp sensor (TH)

 

 

 

 

1 side

 

I/F

overheat error

 

was overheated.

 

 

 

 

02: Compressor

 

 

 

 

 

 

 

 

 

 

2 side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P10

P10

Indoor address

Ob

Indoor

Indoor

All stop

• Float switch operated.

 

 

 

 

with trouble

 

 

overflow error

 

• Float switch circuit

 

 

 

 

 

 

 

 

 

disconnected or the

 

 

 

 

 

 

 

 

 

connector came off.

 

 

 

 

 

 

 

 

 

 

 

 

 

P12

11

Indoor

Indoor fan

Corresponding

• The value of motor speed

 

 

 

 

 

 

 

motor error

unit only stops.

deviated from target value

 

 

 

 

 

 

 

 

 

was detected for certain time.

 

 

The standard ducted unit air conditioner utilizes a direct current (DC) indoor fan motor that features current

 

 

Over-current protection

 

limiting protection. In the event power is not isolated prior to service, the protective control circuit will activate

operated.

 

and stop the unit operating.The check code “P12”will be displayed on the remote controller-once service work

 

 

 

 

has been completed, this code can be cleared by switching off then on the electrical isolation device of the

 

 

 

 

indoor unit and pressing the operation stop button on the remote controller to reset the system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P13

P13

47

I/F

Outdoor liquid

All stop

In heating

 

 

 

 

 

 

back

 

While the system is operating

 

 

 

 

 

 

detection

 

in HEAT mode, outdoor PMV of • Check clogging of SV2 circuit.

133

 

 

 

 

 

error

 

which opening degree was 100

 

 

 

 

 

 

 

pulse or less for a certain time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P15

P15

01: TS condition

AE

I/F

Gas leak

All stop

Suction temp exceeded the

 

 

 

 

 

 

detection

 

judgment standard temp for 10

 

 

 

 

 

 

(TS1

 

minutes or more.

 

 

 

 

 

 

condition)

 

 

 

 

02: TD condition

AE

I/F

Gas leak detection (TD condition)

All stop

Page 133
Image 133
Toshiba MMU-AP0091H service manual 133, Heating