Toshiba MMU-AP0091H service manual Central control mode 1 Cannot operate

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 63
Image 63

No.

Item

Outline of specifications

Remarks

 

 

 

 

15

“ ” and “ ”

<Operation standby> .......... Display on remote controller

• “ ” goes on.

 

display

(1) • “P05” is one of displays of power wire missing.

 

 

(Operation and

• “P05” of power cable is detected.

 

 

heating stand-by)

 

 

• “COOL/DRY” operation cannot be performed because the

 

 

 

 

 

 

other indoor unit is under “HEAT” operation.

 

 

 

• “HEAT” operation cannot be performed because COOL

 

 

 

priority is set (Outdoor I/F P.C. board SW11 1-bit is ON)

 

 

 

and the other indoor unit is under “COOL/DRY” operation.

 

 

 

• “FAN” operation cannot be performed because the system

 

 

 

performs “Heat oil/Refrigerant recovery” operation.

 

 

 

• There is a unit in which indoor overflow “P10” is detected.

 

 

 

• There is a unit in which interlock alarm “P23” is detected.

 

 

 

(2) The above indoor units unavailable to operate waits under

 

 

 

condition of thermostat OFF.

• “ ” goes on.

 

 

 

 

 

<HEAT standby> .................. Display on remote controller

 

(1)• HEAT thermostat is OFF.

During HEAT operation, the fan rotates with lower air speed than one specified in order to prevent discharge of cold draft or stops. (including case that defrost operation is being performed)

“HEAT” operation cannot be performed because COOL priority is set (Outdoor I/F P.C. board SW11 bit 1 is ON) and the other indoor unit is under “COOL/DRY” operation.

(2)“HEAT standby” is displayed until the above conditions are released.

16 Selection of

(1) The contents which can be changed on the remote controller

 

central control

at indoor unit side can be selected by setup at the central

 

mode

controller side.

 

 

(2) In case of operation from TCC-LINK central controller

 

 

(TCB-SC642TLE, etc.)

 

 

[Central control mode 1] : Cannot operate

 

 

[Central control mode 2] :

 

 

Cannot operate, stop, select mode, set up temp.

 

 

[Central control mode 3] :

 

 

Cannot select mode, set up temp.

 

 

[Central control mode 4] : Cannot select mode

If operation is performed

 

(3) RBC-AMT21E (Wired remote controller)

 

from the remote

 

While mode is the central control mode, “ CENTRAL”

 

controller “CENTRAL

 

lights on the display part of the remote controller.

CONTROL” mode, the

 

 

status is notified with

 

 

receiving sound.

63